Baldor VFD Fault Codes
The fault messages of Baldor Series H drives, the 15H inverter control and the 18H flux vector control (with the 15V and 23H where Baldor prints the same message), as the keypad shows them: what each one means, the likely causes, the first checks, and how to log it so it stops coming back. Baldor's VS1 manuals are not on a Baldor or ABB site, so the VS1 is not covered.
How faults show
Series H controls (Baldor names 15H, 17H, 18H, 19H, 20H, 21H and 22H) all use the same keypad and display. The keypad has a backlit 2 line by 16 character LCD. When a fault occurs, motor operation stops and the fault message (for example HW Desaturation on a 15H or DC Bus High on an 18H) is shown on the keypad display.
The control keeps a log of the last 31 faults with the time each one occurred; when more occur, the oldest is deleted. To read the log: from display mode press DISP to scroll to the Fault Log entry point (5 presses on the 18H), press ENTER to show the first fault type and time, and use the arrow key to scroll through the messages.
To clear the log: at the Fault Log entry point press ENTER, then SHIFT, RESET, SHIFT and ENTER. Diagnostic Info (press DISP to the diagnostic block, then ENTER) shows control temperature, bus voltage, % overload current remaining, the opto input and output states, running time, the power base ID and the installed expansion boards, which helps with overload, temperature and base ID faults.
To reset: fix the cause, then press RESET on the keypad (in local mode). In Standard Run 3 Wire mode, closing J4-15 (15H) or J1-15 (18H) also resets a fault.
In the Level 2 Miscellaneous block, Restart Auto/Man set to Automatic with Restart Fault/Hr above zero makes the control reset itself after the Restart Delay and run again; with Restart Fault/Hr at zero the fault must be reset by hand. On the 18H, the Overload parameter can be set to Foldback (reduce current) instead of Fault (trip).
If the display is blank, adjust the contrast: press DISP, SHIFT twice, the arrow keys, then ENTER.
Do not touch any circuit board, power device or electrical connection until you have made sure power is disconnected and no high voltage is present from this equipment or equipment connected to it. Do not remove the cover for at least five (5) minutes after AC power is disconnected, to allow the capacitors to discharge.
The motor circuit may have high voltage whenever AC power is applied, even when the motor is not rotating. The unit has an automatic restart feature: if an automatic restart could injure someone, set Restart Auto/Man to Manual, and do not use motor overload relays with automatic reset. Improper operation can cause violent motion of the motor shaft and driven equipment.
Dynamic brake resistors can get hot enough to ignite combustible materials. Disconnect motor leads T1, T2 and T3 from the control before a Megger test on the motor. Most troubleshooting needs only a digital voltmeter with at least 1 megohm input impedance. Sources: MN715 (9/03) Safety Notice and precautions, PDF pages 10 and 11, and Section 5, PDF page 72.
MN718 (5/99) Safety Notice and precautions, PDF pages 10 and 11, and Section 5, PDF page 74. Follow lockout/tagout and your site's safe-work procedures, and check the manual for your exact model before you act.
Quick lookup
Faults stop the motor and the machine, so in OEE they are availability losses.
Type a message or a word (overcurrent, bus, ground, encoder) to filter the list. Click a message for its causes and first checks. The same message can mean different things on the 15H and the 18H, so each series has its own row.
54 codes
| Message | Series | Description |
|---|---|---|
| Invalid Base ID | 15H | Failure to determine control horsepower and input voltage configuration from the Power Base ID value in software |
| NV Memory Fail | 15H | Failure to read or write to non-volatile memory |
| Param Checksum | 15H | Parameter Checksum error detected |
| Low INIT Bus V | 15H | Low bus voltage detected on startup |
| HW Desaturation | 15H | High output current condition detected (greater than 400% of rated output current) |
| HW Surge Current | 15H | High output current condition detected (greater than 250% of rated output current) |
| HW Ground Fault | 15H | Ground Fault detected (output current leakage to ground) |
| HW Power Supply | 15H | Control Board power supply failure detected |
| Hardware Protect | 15H | A general hardware fault was detected but cannot be isolated |
| 1 MIN Overload | 15H | Peak output current exceeded the 1 minute rating value |
| 3 SEC Overload | 15H | Peak output current exceeded the 3 second rating value |
| Overcurrent | 15H | Continuous current limit exceeded |
| BUS Overvoltage | 15H | High DC Bus voltage |
| Bus Undervoltage | 15H | Low DC Bus voltage condition detected |
| Heat Sink Temp | 15H | Control heatsink exceeded upper temperature limit |
| External Trip | 15H | Connection between J4-16 and J4-17 is open |
| New Base ID | 15H | Control board detected a change in the Power Base ID value in software |
| REGEN RES Power | 15H | Excessive power dissipation required by Dynamic Brake Hardware |
| EXB Selection | 15H | Expansion board not installed to support the selected Level 1 Input Block, Command Select parameter |
| Torque Proving | 15H | Unbalanced current in the three phase motor leads |
| Unknown FLT Code | 15H | Microprocessor detected a fault that is not identified in the fault code table |
| µP RESET | 15H | A software watchdog timer has reset the processor because a process has timed out |
| FLT Log MEM Fail | 15H | Corrupt data in fault log (may occur on older systems only) |
| Current SENS FLT | 15H | Failure to sense phase current |
| Bus Current SENS | 15H | Failure to sense bus current |
| Over Speed | 15H | Motor exceeded 110% of MAX Output Freq parameter value |
| Current Sens FLT | 18H | Defective phase current sensor or open circuit detected between control board and current sensor |
| DC Bus High | 18H | Bus over voltage condition occurred |
| DC Bus Low | 18H | Bus under voltage condition occurred |
| Encoder Loss | 18H | Noise on encoder lines, encoder power supply loss, encoder coupling slipping or broken, defective encoder or defective wiring |
| External Trip | 18H | An external over temperature condition occurred or open circuit on J1-16 |
| Following Error | 18H | Excessive following error detected between command and feedback signals |
| GND FLT | 18H | Low impedance path detected between an output phase and ground |
| INT Over-Temp | 18H | Temperature of control heatsink exceeded safe level |
| Invalid Base ID | 18H | Control does not recognize power base ID |
| Inverter Base ID | 18H | Control board installed on power base without current feedback |
| Logic Supply FLT | 18H | Logic power supply not working properly |
| Lost User Data | 18H | Battery backed RAM parameters have been lost or corrupted |
| Low INIT Bus V | 18H | Insufficient bus voltage on start-up |
| Memory Error | 18H | EEPROM error occurred |
| New Base ID | 18H | Control board was changed since last operation |
| No EXB Installed | 18H | Programmed operating mode requires an expansion board |
| Over Current FLT | 18H | Instantaneous over current condition detected by bus current sensor |
| Overload - 1 min | 18H | Output current exceeded 1 minute rating |
| Overload - 3 sec | 18H | Output current exceeded 3 second rating |
| Over speed | 18H | Motor RPM exceeded 110% of programmed MAX Motor Speed |
| µP Reset | 18H | Power applied before the Bus voltage reached 0VDC |
| PWR Base FLT | 18H | Desaturation of power device occurred or bus current threshold exceeded |
| Regen R PWR FLT | 18H | Regen power exceeded Dynamic Brake value (Level 2 Brake Adjust resistor rating) |
| Resolver Loss | 18H | Resolver feedback problem is indicated (if resolver used) |
| Torque Prove FLT | 18H | Unbalanced current between all 3 motor phases |
| User Fault Text | 18H | Custom software operating fault occurred |
| Unknown Fault | 18H | Fault occurred but cleared before its source could be identified |
| Power Module | 18H | Power supply failure |
Each code: causes and first checks
Invalid Base ID: Failure to determine control horsepower and input voltage configuration from the Power Base ID value in software
Hits OEE: AvailabilityWhat it means: The control board cannot work out the horsepower and input voltage of the power section it is fitted to, because it does not recognize the Power Base ID.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Control does not recognize the hp and voltage configuration of the power base
First checks, in this order
- Press RESET on the keypad.
- If the fault remains, open Diagnostic Info and compare the reported power base ID with Table 5-2 Power Base ID in MN715 for your catalog number.
- If the ID is different from the table, call Baldor.
NV Memory Fail: Failure to read or write to non-volatile memory
Hits OEE: AvailabilityWhat it means: The control could not read from or write to its non-volatile memory, where the parameter settings are kept.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Memory fault in the control
First checks, in this order
- Press RESET on the keypad.
- Restore the parameter values to factory settings, then re-enter your own settings.
- If the fault remains, call Baldor.
Param Checksum: Parameter Checksum error detected
Hits OEE: AvailabilityWhat it means: The checksum of the stored parameters does not match, so the parameter data may be corrupt.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Memory fault in the control
First checks, in this order
- Press RESET on the keypad.
- Restore the parameter values to factory settings, then re-enter your own settings.
- If the fault remains, call Baldor.
Low INIT Bus V: Low bus voltage detected on startup
Hits OEE: AvailabilityWhat it means: When power was applied, the DC bus did not charge to a high enough voltage.[1][2][5][3]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Improper (low) AC line voltage (cause given for the same message in the Series 18H manual MN718)
First checks, in this order
- Check the input AC voltage level at the control.
- Disconnect the dynamic brake hardware and retry (corrective action printed for the same message in MN718).
- Check that the supply matches the model voltage range, for example 180 to 264 VAC 3 phase 60 Hz on 230 VAC models and 342 to 528 VAC 3 phase 60 Hz on 460 VAC models (MN715 specifications).
HW Desaturation: High output current condition detected (greater than 400% of rated output current)
Hits OEE: AvailabilityWhat it means: Output current spiked above about 400% of the control's rated output current and the hardware desaturation protection tripped. On size B2 controls Baldor says a desat error can also mean low line impedance, a brake transistor failure or an internal output transistor overtemperature.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Accel or Decel rate set too short
- Torque Boost set too high
- Electrical noise in the logic circuits
- Motor overloaded
- Size B2 controls: low line impedance, brake transistor failure or output transistor overtemperature
First checks, in this order
- Lengthen the Accel and Decel rates.
- Reduce the torque boost value.
- Check grounding of the power wiring and shielding of the signal wiring.
- Verify the control and motor are sized correctly, or reduce the motor load.
- On size B2 controls check the supply line impedance: MN715 asks for 1% minimum on B2, C2, D2, F, G, G2, G+ and H sizes and 3% minimum on A, B, C, D and E sizes.
HW Surge Current: High output current condition detected (greater than 250% of rated output current)
Hits OEE: AvailabilityWhat it means: Output current went above about 250% of the control's rated output current.[1][2][5][6]
Also on: 15V (MN715V lists the same message and description). Series 15J (MN715J) lists the same message and description; the checks above are the corrective actions MN715J prints for it.
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Output current surge, for example while the motor is ramping (motor, coupling or load problem)
- Accel time too short
- Torque boost set wrong
First checks, in this order
- Turn power off and on (cycle power).
- If it tripped while ramping the motor, check the motor, the coupling and the load.
- Increase the Accel time.
- Increase or decrease the torque boost value.
- Press RESET. If the fault remains, contact Baldor.
HW Ground Fault: Ground Fault detected (output current leakage to ground)
Hits OEE: AvailabilityWhat it means: Motor current is leaking to ground somewhere in the motor leads or inside the motor.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Output (motor) current leakage to ground
- Motor internally shorted to ground
- Motor lead wire with high capacitance
First checks, in this order
- Disconnect the wiring between the control and the motor and retry the test.
- If the fault clears, reconnect the motor leads and retry. Repair the motor if it is internally shorted.
- Replace the motor lead wire with low capacitance cable.
- If the ground fault remains with the motor disconnected, contact Baldor.
- Before any Megger (insulation) test on the motor, disconnect motor leads T1, T2 and T3 from the control, or the control will be badly damaged.
HW Power Supply: Control Board power supply failure detected
Hits OEE: AvailabilityWhat it means: The power supply that feeds the control board has failed.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Power supply malfunction
First checks, in this order
- With power removed and the 5 minute discharge wait done, check the internal connections.
- Baldor's corrective action is to replace the logic power board.
Hardware Protect: A general hardware fault was detected but cannot be isolated
Hits OEE: AvailabilityWhat it means: The control saw a hardware fault but it lasted too short a time to tell which one.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Fault duration too short to be identified
First checks, in this order
- Reset the control.
- Check grounding of the power wiring and shielding of the signal wiring.
- If the fault keeps returning, Baldor's corrective action is to replace the control board.
1 MIN Overload: Peak output current exceeded the 1 minute rating value
Hits OEE: AvailabilityWhat it means: Output current stayed above the 1 minute overload rating for too long. MN715 rates overload capacity at 150% for 60 seconds in Constant Torque mode and 115% for 60 seconds in Variable Torque mode.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Motor overloaded
- PK Current Limit setting
- ACCEL or DECEL times too short
- Control and motor not sized for the load
First checks, in this order
- Check the PK Current Limit parameter in the Level 2 Output Limits block.
- Check the motor for overloading.
- Increase the ACCEL and DECEL times.
- Reduce the motor load.
- Verify the control and motor are sized correctly.
- Diagnostic Info shows the % overload current remaining.
3 SEC Overload: Peak output current exceeded the 3 second rating value
Hits OEE: AvailabilityWhat it means: Output current went above the short time peak rating. MN715 rates it at 170 to 200% for 3 seconds in Constant Torque mode.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Motor overloaded
- PK Current Limit setting
- ACCEL time too short
- Control and motor not sized for the load
First checks, in this order
- Check the PK Current Limit parameter in the Level 2 Output Limits block.
- Check the motor for overloading.
- Increase the ACCEL time.
- Reduce the motor load.
- Verify the control and motor are sized correctly.
Overcurrent: Continuous current limit exceeded
Hits OEE: AvailabilityWhat it means: Output current stayed above the control's continuous current limit.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Load current above the continuous rating of the control
First checks, in this order
- Read the fault log to see when it tripped and which faults came with it.
- Check the motor for overloading and verify the control and motor are sized correctly (Baldor's corrective action for the 15H overload messages).
- Check that all power and control wiring is correct and installed as the manual recommends before contacting Baldor.
BUS Overvoltage: High DC Bus voltage
Hits OEE: AvailabilityWhat it means: The DC bus voltage went too high, usually from energy coming back from the motor while it slows down. The 15H troubleshooting table lists this indication as Bus Overvoltage Trip or HW Overvoltage.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Excessive dynamic braking power
- DECEL rate set too low a value (decel too fast)
- Overhauling motor load
- Dynamic brake miswired
- Input voltage too high
First checks, in this order
- Check the dynamic brake watt and resistance parameter values.
- Lengthen the DECEL time.
- Add external dynamic braking: an RGA resistor kit or an RBA transistor assembly.
- Correct the problem with the overhauling motor load.
- Check the dynamic brake hardware wiring.
- Verify the AC line voltage. Use a step down transformer if needed and a line reactor to minimize spikes.
Bus Undervoltage: Low DC Bus voltage condition detected
Hits OEE: AvailabilityWhat it means: The DC bus voltage dropped too low, usually because the AC supply sagged or is too low.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Input voltage too low
- Power line sags, for example when other equipment starts
First checks, in this order
- Verify the AC line voltage. Use a step up transformer if needed.
- Check for power line disturbances such as sags caused by other equipment starting.
- Monitor the power line with a date and time imprint to isolate the power problem.
- Disconnect the dynamic brake hardware and repeat the operation.
Heat Sink Temp: Control heatsink exceeded upper temperature limit
Hits OEE: AvailabilityWhat it means: The control's heatsink got too hot. On size B2 controls the main heatsink or the gate drive circuit board may be too hot.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Motor overloaded
- Ambient temperature too high
- Built in fans ineffective or not running
First checks, in this order
- Correct the motor loading and verify the control and motor sizing.
- Move the control to a cooler area, or add cooling fans or air conditioning to the cabinet. MN715 rates the control for 0 to 40 degrees C, derated 2% per degree C above 40 up to 55 degrees C maximum.
- Verify the fans run, remove debris from the fan and heatsink surfaces, and replace the fan or check fan wiring.
- Diagnostic Info shows the control temperature in degrees C.
External Trip: Connection between J4-16 and J4-17 is open
Hits OEE: AvailabilityWhat it means: The external trip input (usually the motor thermostat) opened. With Level 2 Protection block External Trip set to ON, opening the normally closed contact at J4-16 (to J4-17) shuts the drive down.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: the control disables and the motor coasts to a stop; the fault is logged
Likely causes
- Motor ventilation insufficient
- Motor drawing excessive current
- Volts/Hertz ratio wrong
- No thermostat connected
- Poor thermostat connections
- External Trip parameter set ON with nothing wired to J4-16
First checks, in this order
- Clean the motor air intake and exhaust, check the external blower and verify the motor's internal fan is coupled securely.
- Check the motor for overloading and verify the control and motor sizing.
- Adjust the Volts/Hz parameter, the Base Frequency and the Max Output Voltage.
- Connect the thermostat and verify all external trip circuits used with it, or disable the thermostat input at the control.
- Check the thermostat connections.
- If nothing is wired to J4-16, set External Trip to OFF.
New Base ID: Control board detected a change in the Power Base ID value in software
Hits OEE: AvailabilityWhat it means: The control board found itself on a different power base than before, typically after a control board or circuit board was replaced.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Control or circuit board replaced
First checks, in this order
- Restore the parameters to factory settings.
- Reset the control.
- Then re-enter your application settings.
REGEN RES Power: Excessive power dissipation required by Dynamic Brake Hardware
Hits OEE: AvailabilityWhat it means: The braking energy the drive has to dump into the dynamic brake resistor is more than the resistor rating set in the control.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Incorrect dynamic brake parameter
- Regen power exceeded the dynamic brake resistor rating
First checks, in this order
- Check the Resistor Ohms and Resistor Watts parameters in the Level 2 Brake Adjust block.
- Add external dynamic braking: an RGA resistor kit or an RBA transistor assembly.
- Increase the Decel Time.
EXB Selection: Expansion board not installed to support the selected Level 1 Input Block, Command Select parameter
Hits OEE: AvailabilityWhat it means: The operating mode chosen in Command Select needs an expansion board that is not fitted. The 15H troubleshooting table lists this under the indication Command Select.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Incorrect operating mode programmed
- Expansion board needed for the selected mode is not installed
First checks, in this order
- Change the Operating Mode in the Level 1 Input block to one that does not require the expansion board.
- Or install the correct expansion board for the selected operating mode.
- Diagnostic Info shows which Group 1 or Group 2 expansion boards are installed.
Torque Proving: Unbalanced current in the three phase motor leads
Hits OEE: AvailabilityWhat it means: The output current in the three motor phases is not balanced, which can mean an open phase or a bad connection between the drive and the motor.[1][2][5][3]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Unbalanced current in the 3 motor phases
First checks, in this order
- Check continuity from the control to the motor windings and verify the motor connections (corrective action printed for the matching Torque Prove FLT message in MN718).
Unknown FLT Code: Microprocessor detected a fault that is not identified in the fault code table
Hits OEE: AvailabilityWhat it means: The control logged a fault that is not in its fault code table.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Microprocessor detected a fault that is not defined in the fault code table
First checks, in this order
- Press RESET on the keypad.
- Restore the parameter values to factory settings.
- If the fault remains, call Baldor.
µP RESET: A software watchdog timer has reset the processor because a process has timed out
Hits OEE: AvailabilityWhat it means: The microprocessor was restarted by its own watchdog because a software process took too long. On the 18H the similar message means something else, see that row.[1][2][5]
Also on: 15V (MN715V lists the same message and description). The 15H troubleshooting table prints it as uP Reset.
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Software process timed out
First checks, in this order
- Press RESET on the keypad.
- If the fault remains, call Baldor.
FLT Log MEM Fail: Corrupt data in fault log (may occur on older systems only)
Hits OEE: AvailabilityWhat it means: The fault log memory holds corrupt data.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Corrupt data in the fault log, mainly on older systems
First checks, in this order
- Press RESET on the keypad.
- If the fault remains, call Baldor.
Current SENS FLT: Failure to sense phase current
Hits OEE: AvailabilityWhat it means: The control cannot read the output phase current.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Phase current sensing failure
First checks, in this order
- Press RESET on the keypad.
- If the fault remains, call Baldor.
Bus Current SENS: Failure to sense bus current
Hits OEE: AvailabilityWhat it means: The control cannot read the DC bus current.[1][2][5]
Also on: 15V (MN715V lists the same message and description)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Bus current sensing failure
First checks, in this order
- Press RESET on the keypad.
- If the fault remains, call Baldor.
Over Speed: Motor exceeded 110% of MAX Output Freq parameter value
Hits OEE: AvailabilityWhat it means: Output frequency went above 110% of the maximum output frequency set in the control.[1][2][5]
Also on: 15V (the MN715V troubleshooting table prints the same indication)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Motor driven above 110% of the MAX Output Freq setting
First checks, in this order
- Check Max Output Freq in the Level 2 Output Limits block.
Current Sens FLT: Defective phase current sensor or open circuit detected between control board and current sensor
Hits OEE: AvailabilityWhat it means: The control lost the signal from a phase current sensor, either because the sensor failed or because its connection to the control board is open.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Open circuit between the control board and the current sensor
- Defective current sensor
First checks, in this order
- With power off and the 5 minute discharge wait done, check the connections between the control board and the current sensor.
- Replace the current sensor if it is defective.
DC Bus High: Bus over voltage condition occurred
Hits OEE: AvailabilityWhat it means: The DC bus voltage went too high, usually from braking energy coming back from the motor or a high supply voltage.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Excessive dynamic braking power
- Dynamic brake miswiring
- Input voltage too high
- Decel rate too fast (listed in the 23H manual)
First checks, in this order
- Increase the DECEL time.
- Check the dynamic brake watt and resistance parameter values.
- Add optional dynamic braking hardware.
- Check the dynamic brake hardware wiring.
- Verify the AC line voltage. Use a step down isolation transformer if needed and a line reactor to minimize spikes.
DC Bus Low: Bus under voltage condition occurred
Hits OEE: AvailabilityWhat it means: The DC bus voltage dropped too low, usually because the AC supply is low or sagged.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Input voltage too low
- Power line sags, for example when other equipment starts
First checks, in this order
- Verify the AC line voltage. Use a step up isolation transformer if needed.
- Check for power line disturbances such as sags caused by other equipment starting.
- Monitor the power line with a date and time imprint to isolate the power problem.
- Disconnect the dynamic brake hardware and repeat the operation.
Encoder Loss: Noise on encoder lines, encoder power supply loss, encoder coupling slipping or broken, defective encoder or defective wiring
Hits OEE: AvailabilityWhat it means: The control lost a valid encoder feedback signal from the motor.[3]
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Encoder power supply failure
- Encoder coupling slipping, broken or misaligned
- Excessive noise on the encoder lines
- Defective encoder or defective wiring
First checks, in this order
- Check for 5 VDC at J1-29 and J1-30, and for +5 VDC and ground at the encoder end pins.
- Correct or replace the encoder to motor coupling.
- Check the position counter in Diagnostic Information for jittering, which confirms an encoder problem.
- Check the encoder connections, separate the encoder leads from power wiring and cross encoder and power wires at 90 degrees.
- Electrically isolate the encoder from the motor, or install the optional Isolated Encoder Feedback expansion board.
External Trip: An external over temperature condition occurred or open circuit on J1-16
Hits OEE: AvailabilityWhat it means: The external trip input (usually the motor thermostat) opened. With Level 2 Protection block External Trip set to ON, opening the normally closed contact at J1-16 shuts the drive down.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: the control disables and the motor coasts to a stop; the fault is shown and logged
Likely causes
- Motor ventilation insufficient
- Motor drawing excessive current
- No thermostat connected
- Poor thermostat connections
- External Trip parameter set ON with nothing wired to J1-16
First checks, in this order
- Clean the motor air intake and exhaust, check the external blower and verify the motor's internal fan is coupled securely.
- Check the motor for overloading and verify the control and motor sizing.
- Connect the thermostat and verify all external trip circuits used with it, or disable the thermostat input at J1-16.
- Check the thermostat connections.
- If nothing is wired to J1-16, set External Trip to OFF in the Level 2 Protection block.
- Use a dry contact thermostat that needs no external power; power on the J1-16 and J1-17 leads can damage the control.
Following Error: Excessive following error detected between command and feedback signals
Hits OEE: AvailabilityWhat it means: Actual speed fell outside the allowed band around the commanded speed. This trip only happens when Following Error is ON in the Level 2 Protection block; the band is the Level 1 Output block AT Speed Band.[3]
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Speed proportional gain set too low
- Current limit set too low
- ACCEL or DECEL time too short
- Excessive load
First checks, in this order
- Increase the Speed PROP Gain parameter.
- Increase the Current Limit parameter.
- Increase the ACCEL and DECEL times.
- Verify the control and motor are sized correctly for the load.
- Check the AT Speed Band setting in the Level 1 Output block.
GND FLT: Low impedance path detected between an output phase and ground
Hits OEE: AvailabilityWhat it means: One of the output phases has a low resistance path to ground, in the wiring or in the motor.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Improper wiring
- Wiring shorted in the conduit
- Motor winding shorted
First checks, in this order
- Disconnect the wiring between the control and the motor and retry the test.
- If GND FLT clears, reconnect the motor leads and retry. Rewire as necessary or repair the motor.
- If GND FLT remains with the motor disconnected, contact Baldor.
- Before any Megger (insulation) test on the motor, disconnect motor leads T1, T2 and T3 from the control, or the control will be badly damaged.
INT Over-Temp: Temperature of control heatsink exceeded safe level
Hits OEE: AvailabilityWhat it means: The control's heatsink got too hot.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Motor overloaded
- Ambient temperature too high
- Cooling fans clogged or air path restricted (listed in the 23H manual)
First checks, in this order
- Correct the motor loading and verify the control and motor sizing.
- Move the control to a cooler area, or add cooling fans or air conditioning to the cabinet. MN718 rates the control for minus 10 to plus 40 degrees C, derated 2% per degree C above 40 up to 55 degrees C maximum.
- Clean the fans and the air path.
- Diagnostic Info shows the control temperature.
Invalid Base ID: Control does not recognize power base ID
Hits OEE: AvailabilityWhat it means: The control board does not recognize the horsepower and voltage configuration of the power base it is fitted to.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Control does not recognize the HP and voltage configuration
First checks, in this order
- Press RESET on the keypad.
- If the fault remains, call Baldor.
- Diagnostic Info shows the power base ID as a hexadecimal value; Table 5-3 of MN718 lists the expected ID for each catalog number.
Inverter Base ID: Control board installed on power base without current feedback
Hits OEE: AvailabilityWhat it means: The 18H vector control board is fitted to a power base that has no output phase current sensors.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Power base with no output phase current sensors being used
First checks, in this order
- Replace the power base with one that has output leg current feedback. Contact Baldor.
Logic Supply FLT: Logic power supply not working properly
Hits OEE: AvailabilityWhat it means: The logic power supply inside the control is not working properly.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Power supply malfunction
First checks, in this order
- Baldor's corrective action is to replace the logic power supply. Remove power and wait at least 5 minutes before opening the cover.
Lost User Data: Battery backed RAM parameters have been lost or corrupted
Hits OEE: AvailabilityWhat it means: The parameters held in battery backed memory were lost or corrupted. When the fault is cleared (Reset), the control resets to factory preset values.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: after RESET the control returns to factory preset values
Likely causes
- Battery backed memory failure
First checks, in this order
- Disconnect power to the control and apply power again (cycle power).
- Enter all parameters again, for example from the User Settings recorded at the end of the manual.
- Cycle power. If the problem persists, contact Baldor.
Low INIT Bus V: Insufficient bus voltage on start-up
Hits OEE: AvailabilityWhat it means: When power was applied, the DC bus did not charge to a high enough voltage.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Improper AC line voltage
First checks, in this order
- Disconnect the dynamic brake hardware and retry.
- Check the input AC voltage level, for example 180 to 264 VAC 3 phase 60 Hz on 230 VAC models and 340 to 528 VAC 3 phase 60 Hz on 460 VAC models (MN718 specifications).
Memory Error: EEPROM error occurred
Hits OEE: AvailabilityWhat it means: The control's EEPROM memory reported an error.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- EEPROM memory fault
First checks, in this order
- Press RESET on the keypad.
- If the fault remains, call Baldor.
New Base ID: Control board was changed since last operation
Hits OEE: AvailabilityWhat it means: The control board found itself on a different power base than at the last power up, typically after a board change, and its parameters are not yet set up for it.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Software parameters not initialized on a newly installed control board
First checks, in this order
- Press RESET on the keypad to clear the fault.
- Cycle power (turn power off, then on).
- Reset the parameter values to factory settings.
- Open Diagnostic Info and compare the power base ID with Table 5-3 of MN718 to make sure they match.
- Re-enter the parameter block values recorded in the User Settings at the end of the manual.
- Autotune the control.
No EXB Installed: Programmed operating mode requires an expansion board
Hits OEE: AvailabilityWhat it means: The operating mode set in the control needs an expansion board that is not installed.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Incorrect operating mode programmed
- Expansion board needed for the selected mode is not installed
First checks, in this order
- Change the Operating Mode in the Level 1 Input block to one that does not require an expansion board.
- Or install the correct expansion board for the selected operating mode.
- Diagnostic Info shows which Group 1 or Group 2 expansion boards are installed.
Over Current FLT: Instantaneous over current condition detected by bus current sensor
Hits OEE: AvailabilityWhat it means: The bus current sensor saw an instant current spike above the trip level.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Current Limit parameter set lower than the drive rating
- ACCEL or DECEL time too short
- Excessive load
- Encoder coupling slipping, broken or misaligned, or encoder bearing failure
- Excessive noise on the encoder lines
- Electrical noise from external DC or AC relay coils
First checks, in this order
- Increase the PK Current Limit parameter in the Level 2 Output Limits block (MN723 adds: not above the drive rating).
- Increase the ACCEL and DECEL parameters in the Level 1 ACCEL/DECEL Rate block.
- Reduce the motor load and verify the control and motor sizing.
- Correct or replace the encoder to motor coupling; replace the encoder if its bearing has failed.
- Check the position counter in Diagnostic Information for jittering, check the encoder connections and route encoder leads away from power wiring.
- Install reverse biased diodes across external DC relay coils and RC snubbers on external AC coils.
Overload - 1 min: Output current exceeded 1 minute rating
Hits OEE: AvailabilityWhat it means: Output current stayed above the 1 minute overload rating for too long. MN718 rates overload capacity at 150% for 60 seconds in Constant Torque mode and 115% for 60 seconds in Variable Torque mode.[3][4]
Also on: 23H AC servo control (MN723 lists the same message). Its troubleshooting table prints Overload - 1 Min FLT.
Drive response: with Overload set to Fault the control trips and must be reset; with Foldback it reduces output current instead
Likely causes
- Peak output current above the 1 minute rating
- Motor overloaded
- ACCEL or DECEL times too short
- Encoder coupling slipping, broken or misaligned, or encoder bearing failure
First checks, in this order
- Check the PK Current Limit parameter in the Level 2 Output Limits block.
- If continuous running is wanted, change the Overload parameter in the Level 2 Protection block from Trip (Fault) to Foldback, which reduces output current instead of tripping.
- Check the motor for overloading, increase the ACCEL and DECEL times and reduce the load.
- Verify the control and motor are sized correctly.
- Correct or replace the encoder coupling, and replace the encoder if its bearing has failed.
Overload - 3 sec: Output current exceeded 3 second rating
Hits OEE: AvailabilityWhat it means: Output current went above the short time peak rating. MN718 rates it at 170 to 200% for 3 seconds in Constant Torque mode.[3][4]
Also on: 23H AC servo control (MN723 lists the same message). Its troubleshooting table prints Overload - 3 Sec FLT.
Drive response: with Overload set to Fault the control trips and must be reset; with Foldback it reduces output current instead
Likely causes
- Peak output current above the 3 second rating
- Motor overloaded
- ACCEL time too short
- Encoder coupling slipping, broken or misaligned, or encoder bearing failure
First checks, in this order
- Check the PK Current Limit parameter in the Level 2 Output Limits block.
- If continuous running is wanted, change the Overload parameter in the Level 2 Protection block from Trip (Fault) to Foldback.
- Check the motor for overloading, increase the ACCEL time and reduce the load.
- Verify the control and motor are sized correctly.
- Correct or replace the encoder coupling, and replace the encoder if its bearing has failed.
Over speed: Motor RPM exceeded 110% of programmed MAX Motor Speed
Hits OEE: AvailabilityWhat it means: Measured motor speed went above 110% of the maximum speed programmed in the control.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Motor speed above 110% of the programmed maximum
- Speed PROP Gain too low to hold speed (Baldor's corrective action raises it)
First checks, in this order
- Check Max Output Speed in the Level 2 Output Limits block.
- Increase Speed PROP Gain in the Level 1 Vector Control block.
µP Reset: Power applied before the Bus voltage reached 0VDC
Hits OEE: AvailabilityWhat it means: Power was switched back on before the DC bus had fully discharged to 0 V. On the 18H this message is about power cycling, not a processor watchdog (compare the 15H row).[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Power was cycled before the bus voltage reached 0 VDC
First checks, in this order
- Press RESET on the keypad.
- Disconnect power and allow at least 5 minutes for the bus capacitors to discharge before applying power again.
- If the fault remains, call Baldor.
PWR Base FLT: Desaturation of power device occurred or bus current threshold exceeded
Hits OEE: AvailabilityWhat it means: An output power device came out of saturation or the bus current went over its threshold, which points to very high current or a grounding problem.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Improper ground
- Excessive current or excessive load
- Excessive power in the dynamic brake circuit
- Encoder coupling slipping, broken or misaligned, or encoder bearing failure
- Excessive noise on the encoder lines
- Electrical noise from external DC or AC relay coils
First checks, in this order
- Make sure the control has a separate ground wire to earth ground; panel grounding or conduit connections are not sufficient.
- Disconnect the motor leads from the control and retry. If the fault remains, call Baldor.
- Correct the motor load and verify the control and motor sizing.
- Verify the Ohm and Watt parameters of DC injection braking, increase the decel time and add optional dynamic braking hardware.
- Check the encoder coupling, bearing and wiring; separate encoder leads from power wiring.
- Install reverse biased diodes across external DC relay coils and RC snubbers on external AC coils.
Regen R PWR FLT: Regen power exceeded Dynamic Brake value (Level 2 Brake Adjust resistor rating)
Hits OEE: AvailabilityWhat it means: The braking energy sent to the dynamic brake resistor is more than the resistor rating set in the Level 2 Brake Adjust block.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Incorrect dynamic brake parameter
- Regen power exceeded the dynamic brake resistor rating
- Input voltage too high
First checks, in this order
- Check the Resistor Ohms and Resistor Watts parameters in the Level 2 Brake Adjust block.
- Add optional dynamic braking hardware.
- Verify the AC line voltage. Use a step down transformer if needed and a line reactor to minimize spikes.
Resolver Loss: Resolver feedback problem is indicated (if resolver used)
Hits OEE: AvailabilityWhat it means: The control lost a valid resolver feedback signal (only when a resolver is used).[3]
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Defective resolver
- Resolver power supply loss
- Defective wiring
First checks, in this order
- Check the resolver to motor coupling; align or replace it if needed.
- Verify the wiring, using the Resolver to Digital expansion board manual.
- Electrically isolate the resolver from the motor.
Torque Prove FLT: Unbalanced current between all 3 motor phases
Hits OEE: AvailabilityWhat it means: The output current in the three motor phases is not balanced. The check runs when Torque Proving is ON in the Level 2 Protection block.[3]
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Unbalanced current in the 3 motor phases
First checks, in this order
- Check continuity from the control to the motor windings and verify the motor connections.
User Fault Text: Custom software operating fault occurred
Hits OEE: AvailabilityWhat it means: A fault defined by custom software loaded in the control has occurred.[3][4]
Also on: 23H AC servo control (MN723 lists the same message)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Fault detected by custom software
First checks, in this order
- Refer to the custom software fault list.
Unknown Fault: Fault occurred but cleared before its source could be identified
Hits OEE: AvailabilityWhat it means: A fault happened but cleared before the control could tell what caused it.[3][4]
Also on: 23H AC servo control (MN723 troubleshooting table, same indication)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Short lived fault, for example from high frequency noise on the AC line
First checks, in this order
- Check the AC line for high frequency noise.
- Check input switch connections and switching noise (added in the 23H manual).
Power Module: Power supply failure
Hits OEE: AvailabilityWhat it means: A power supply failure was detected.[3][4]
Also on: 23H AC servo control (MN723 troubleshooting table, same indication)
Drive response: motor operation stops and the message shows on the keypad; fix the cause, then press RESET
Likely causes
- Power supply failure
First checks, in this order
- Press RESET on the keypad.
- If the fault remains, call Baldor.
Log it, or the same alarm comes back
A fault stops the motor and the control logs it, so in OEE terms it is a breakdown. Log the message, the machine and the minutes lost; the control keeps only the last 31 faults, so a written log keeps the pattern.
- Reason code: the message plus the drive, for example Baldor 18H DC Bus High, unwinder drive, so an overvoltage that comes back on every fast stop shows up as a pattern.
- Loss bucket: a stop that needs a reset, a part or a technician is an availability loss (breakdown). Stops shorter than your micro-stop threshold go to performance (minor stops). The six big losses page shows where each one belongs.
- What to count: how often each code fires per week and the minutes it costs. Two numbers a week turn "that alarm comes up sometimes" into a ranked list. The MTBF and MTTR calculator and the downtime cost calculator do the math.
The free OEE tracker logs each stop with its reason and turns the week into a downtime Pareto, so the code that costs the most rises to the top.
fabrico.io has a guide to VFD fault codes. A fault message tells you what the drive measured, not what happened at the machine in the seconds before. Fabrico's camera-based OEE software syncs line camera video with machine data, so you can replay the moment the line stopped next to the trip.
Frequently asked questions
What does HW Desaturation mean on a Baldor 15H drive?
HW Desaturation means the 15H saw a very high output current, more than 400% of its rated output current. Baldor lists Accel or Decel rates set too short, torque boost set too high, electrical noise in the logic circuits and an overloaded motor as causes. Lengthen the Accel and Decel rates, reduce torque boost, check grounding of the power wiring and shielding of the signal wiring, and verify the control and motor sizing. On size B2 controls it can also point to low line impedance, a brake transistor failure or an output transistor running too hot.
How do I see and clear the fault log on a Baldor 15H or 18H?
From display mode press DISP until you reach the Fault Log entry point (5 presses on the 18H), then press ENTER to show the most recent fault and the time it occurred, and scroll with the arrow key. The control keeps the last 31 faults. To clear the log, at the Fault Log entry point press ENTER, SHIFT, RESET, SHIFT and ENTER.
How do I reset a fault on a Baldor 18H vector drive?
Fix the cause first, then press RESET on the keypad while in local mode. In Standard Run 3 Wire mode, closing input J1-15 also resets a fault. If Restart Auto/Man in the Level 2 Miscellaneous block is set to Automatic and Restart Fault/Hr is above zero, the control resets itself after the Restart Delay and will start again, so make sure an automatic restart cannot hurt anyone.
What does uP Reset mean on a Baldor drive?
It depends on the series. On a 15H, µP RESET means a software watchdog timer reset the processor because a process timed out: press RESET and call Baldor if it stays. On an 18H, µP Reset means power was applied before the DC bus had dropped to 0 VDC: press RESET, then disconnect power and wait at least 5 minutes for the bus capacitors to discharge before powering up again.
What does External Trip mean on a Baldor 15H?
The connection between J4-16 and J4-17 is open, usually because the motor thermostat opened. Check motor ventilation and the external blower, check the motor for overload, check the Volts/Hz, Base Frequency and Max Output Voltage settings, and check the thermostat wiring. If nothing is wired to J4-16, set External Trip to OFF in the Level 2 Protection block.
Are Baldor VS1 drives still supported by ABB?
ABB's life cycle statement puts the Baldor branded VS1 drives in the Obsolete phase: VS1PF, VS1MD, VS1SM, VS1SP (except NEMA 4X), VS1GV, VS1SD and VS1PM since March 29, 2013, VS1SP NEMA 4X and VS1CTD since January 1, 2014, and VS1MX/S and VS1ST/S since May 31, 2014. The product is not available in that phase. ABB's general replacement guide is ACS355 for VS1MD and VS1SM, ACB530, ACS250 or ACS355 for VS1SP, ACS880 for VS1GV and VS1SD, and ACS150, ACS250 or ACS355 for VS1MX/S and VS1ST/S, subject to the application.
Sources
Codes and meanings follow the manufacturer documentation below. Wording is ours, simplified for the shop floor; the manual for your exact model and software version wins if it differs.
- Baldor Series 15H Inverter Control Installation & Operating Manual, MN715, 9/03, hosted by Baldor (www.baldor.com)
- Baldor Series 15H Inverter Control Installation & Operating Manual, MN715, 9/02, hosted by Baldor (www.baldor.com)
- Baldor Series 18H AC Flux Vector Control Installation & Operating Manual, MN718, 5/99, hosted by Baldor (www.baldor.com)
- Baldor Series 23H AC Servo Control Installation & Operating Manual, MN723, 1/99, hosted by Baldor (www.baldor.com)
- Baldor Series 15V Inverter Control Installation & Operating Manual, MN715V, 7/00, hosted by Baldor (www.baldor.com)
- Baldor Series 15J Inverter Control Installation and Operating Manual, MN715J, 8/02, hosted by Baldor (www.baldor.com)
- Baldor Elevator Application Guide Installation & Operating Manual, MN770, 3/97, hosted by Baldor (www.baldor.com)
- ABB Product life cycle statement VS1 (Baldor branded drives), DRVSRV-EOFS01U-EN Rev A, 2016-12-30, hosted by ABB (library.e.abb.com)
See the moment the drive tripped
Fabrico, a light MES with computer vision, syncs camera footage with machine and timeline data, so you can replay the exact moment the line stopped and review the cause next to the drive's fault. Cameras also catch short stops and a line that is switched on but not producing, the losses nobody writes down. Machines connect through a PLC, a Fabrico IoT device or an AI camera.
Book a Fabrico demoRelated: ABB ACS550 fault codes · NORD inverter error codes · VFD drive troubleshooting · electric motor · conveyor
Other alarm code lookups: FANUC: servo amplifier · spindle amplifier | Siemens: MICROMASTER 440 · MASTERDRIVES · SINAMICS G120 · SINAMICS V90 servo · SINAMICS V20 · SINAMICS G110 | ABB: ACS550 drive · ACS800 drive · robot IRC5 · DCS800 DC drive | Okuma: OSP alarms | Haas: alarm lookup | Mitsubishi: MELSERVO servo · FR-D700 and FR-E700 inverters · FX PLC | Allen-Bradley: Kinetix and Ultra3000 · MicroLogix · PowerFlex 753 and 755 · PowerFlex 70 and 700 · 1336 and 1305 | Yaskawa: V1000 drive · SERVOPACK servo · Motoman robot | Delta: VFD drives · ASDA servo | Eaton: DC1 and SVX9000 drives | Control Techniques: Commander SK and M200 | Kollmorgen: AKD servo | Lenze: SMVector, 8200, 8400, i500 | Magnetek: IMPULSE and DSD 412 | Omron: MX2 and RX inverters · G5 and 1S servo · CP1 and CJ2 PLC | WEG: CFW500, CFW300, CFW11, CFW08 | Hitachi: WJ200 inverter · SJ700 and SJ-P1 | Toshiba: E3, Q9, P9, S15, nC3, AS3 | AutomationDirect: GS10, GS20, GS4, GS1 to GS3 | Festo: CMMT servo drives | Videojet: 1000 Line CIJ printers | Lincoln Electric: Power Wave welders | Fronius: TPS and TPS/i welders | Beckhoff: TwinCAT ADS, NC and BK1120 | Universal Robots: CB3 and e-Series cobots | Pilz: PNOZ safety relays | SICK: S3000, S300, microScan3 | SANYO DENKI: SANMOTION servo | Parker: SSD 590+, 690+, AC10 | KEB: COMBIVERT F5 | Epson: robot RC700, RC90 | B&R: ACOPOS servo | Schneider Electric: Lexium 32 servo | Bosch Rexroth: IndraDrive | Vacon: NX, VACON 100 and 20 | Fuji Electric: FRENIC-Mini, Multi, Ace, MEGA | LS Electric: S100, G100, iG5A | Panasonic: MINAS A6 and A5 servo | Invertek: Optidrive E3, P2, Eco | SEW-Eurodrive: MOVITRAC B and MOVIDRIVE B | HEIDENHAIN: iTNC 530 and TNC | NORD: NORDAC SK 200E and SK 500E