Lincoln Power Wave Error Codes
The error codes of Lincoln Electric Power Wave welding power sources used in robotic and automated cells (S350, S500, R350, R500, 455M and i400): what each one means, the likely causes, the first checks, and how to log it so it stops coming back.
How errors show
Each Power Wave has a two color status light on the case front. Steady green means the system is OK and talking to its ArcLink equipment. Blinking green is normal for the first 1 to 10 seconds after power up or after a system change, while the machine maps its components. Fast blinking green means auto-mapping failed.
Alternating red and green means a non-recoverable fault: the code is flashed in red one digit at a time with a long pause between digits, and several codes are separated by a green flash. Read the code before you switch the machine off.
On the S350, S500, R350 and R500 the input control board also flashes three digit codes that start with 3 (on the R350 its light sits inside, visible through the left case side louvers, with a beeper).
On a 455M a steady red light usually means nothing is plugged into the wire feeder receptacle, and a Power Feed 10/11 display usually shows Err 006 or Err 100 next to the real code. Lincoln's Diagnostics Utility (Power Wave Manager on older manuals, from powerwavesoftware.com) is the preferred way to read codes because it also reads the error log history.
On an i400 used with a FANUC robot, the robot shows the LECO (FANUC#) number listed in the i400 manual, for example 49 for code 31. To clear: fix the cause, then turn the power source off and back on. On S500 and R500 input board codes, Persistent codes need that power cycle, while Temporary codes clear by themselves once the condition is gone.
Electric shock can kill: turn off input power to the power source, and to every other machine in the welding system, at the disconnect switch or fuse box before working inside, never touch electrically hot parts, and never run the machine with covers removed. The main capacitors can hold more than 400 V DC after power is off.
Before touching anything inside, check with a DC voltmeter across the terminals of both capacitors; if voltage is present, wait several minutes for them to discharge (or discharge them with Lincoln's procedure: a 25 ohm, 25 W resistor held with an insulated glove), then measure again.
Sources: Power Wave i400 manual IM10465, D-2 Capacitor Discharge Procedure and E-1 (PDF pages 36 and 37). Power Wave S500+ and S500 manual IM10456-D, installation, maintenance and troubleshooting warnings (PDF pages 21, 47 and 49). Follow lockout/tagout and your site's safe-work procedures, and check the manual for your exact model before you act.
Quick lookup
Errors stop the weld and the cell, so in OEE they are availability losses; a weld cut short also costs quality.
Type a code or a word (overcurrent, thermal, undervoltage, CAN) to filter the list. Click a code for its causes and first checks.
47 codes
| Code | Model | Name |
|---|---|---|
| 36 | S350, S500, R350, R500, 455M, 455M/STT, 455/R, i400 | Thermal error |
| 54 | S350, S500, R350, R500 | Secondary (Output) over current error |
| 54 | i400 | Secondary (output) over current |
| 31 | 455M, 455M/STT, 455/R | Primary overcurrent error |
| 31 | i400 | Primary (Input) overcurrent error |
| 41 | 455M, 455M/STT, 455/R | Secondary overcurrent error |
| 49 | 455M, 455M/STT, 455/R | Single phase error |
| 58 | S350, S500, R350, R500 | Primary Fault error |
| 336 | S350, S500, R350, R500 | Thermal Fault |
| 81 | S500, R350, R500, i400 | Motor Overload |
| 82 | S500, R350, R500, i400 | Motor Overcurrent |
| 83 | S500, R500 | Shutdown #1 Is Open |
| 84 | S500, R500 | Shutdown #2 Is Open |
| 83 | R350, i400 | Shutdown #1 |
| 84 | R350, i400 | Shutdown #2 |
| 32 | 455M, 455M/STT, 455/R | Capacitor "A" under voltage (Left side facing machine) |
| 33 | 455M, 455M/STT, 455/R | Capacitor "B" under voltage (Right side facing machine) |
| 34 | 455M, 455M/STT, 455/R | Capacitor "A" over voltage (Left side facing machine) |
| 35 | 455M, 455M/STT, 455/R | Capacitor "B" over voltage (Right side facing machine) |
| 37 | 455M, 455M/STT, 455/R | Soft start error |
| 43 | 455M, 455M/STT, 455/R | Capacitor delta error |
| 56 | S350, S500, R350, R500 | Chopper communication error |
| 71 | S500, R500 | Secondary (Output) over power error |
| 331 | S350, R350 | Peak input current limit |
| 331 | S500, R500 | Instantaneous Input Current Limit |
| 337 | S350, S500, R350, R500 | Pre-charge timeout |
| 346 | S350, S500, R350, R500 | Transformer primary over current |
| 333 | S350, R350 | Under-voltage lockout |
| 334 | S500, R500 | Startup Current Check Failure |
| 335 | S500, R500 | Startup Voltage Check Failure |
| 338 | S500, R500 | Input Power Limit |
| 341 | S500, R500 | Input Voltage Dropout |
| 347 | S500, R500 | Average Input Current Limit |
| 349 | S500, R500 | Bus Undervoltage |
| 11 | 455M, 455M/STT, 455/R | CAN communication bus off |
| 12 | 455M, 455M/STT, 455/R | User Interface time out error |
| 21 | 455M, 455M/STT, 455/R | Unprogrammed Weld Mode |
| 22 | 455M, 455M/STT, 455/R | Empty Weld Table |
| 23 | 455M, 455M/STT, 455/R | Weld Table checksum error |
| 32 | i400 | Capacitor "A" under voltage (right side facing the Switch PC Board) |
| 33 | i400 | Capacitor bank "B" under voltage (left side facing the Switch PC Board) |
| 34 | i400 | Capacitor "A" over voltage (right side facing the Switch PC Board) |
| 35 | i400 | Capacitor "B" over voltage (left side facing the Switch PC Board) |
| 37 | i400 | Softstart (pre-charge) error |
| 39 | i400 | Misc. hardware fault |
| 43 | i400 | Capacitor delta error |
| 99 | Power Wave STT Module (add-on module for a host Power Wave power source) | STT Status error |
Each code: causes and first checks
36: Thermal error
Hits OEE: AvailabilityWhat it means: The power source has detected over temperature and stops output; the yellow Thermal LED on the front panel is usually lit as well.[1][2][3][4][5][6][7][8][9][10][11]
Also on: Power Wave STT Module (same code and name). i400 on a FANUC robot: LECO (FANUC#) 54.
Device response: output off; fix the cause, then turn power off and on to clear
Likely causes
- Cooling fan not running, running slowly or stalled
- Intake or exhaust louvers blocked, or dirt clogging the cooling channels
- Weld procedure or duty cycle above the machine rating
- Open thermostat circuit: broken wire, loose connection or failed thermostat on the output rectifier, choke or DC bus board
- On S500, S500 CE and R500 units from mid 2014, a defective Rev 2 M22853 fan that stalls (Lincoln service notice 201408004-3)
First checks, in this order
- Check that the fans run. On S350 and S500 they run slowly at idle and at high speed when output is triggered; on 455M and i400 they should run whenever output is on.
- Clear anything blocking the intake or exhaust louvers and blow dust out of the cooling channels.
- Let the machine cool, then reduce the output current, the duty cycle, or both.
- Check the thermostat circuit for broken wires, open connections or faulty thermostats.
- On a 455M or i400, a tripped DC bus board thermostat can come from too much load on the 40 V DC feeder supply; check that load.
- Cycle input power to clear the code once the cause is fixed.
54: Secondary (Output) over current error
Hits OEE: AvailabilityWhat it means: The long term average weld (secondary) current has gone over the machine limit and the machine shuts its output down to protect itself. Limit: 325 A on S350 and R350; 325 A single phase or 575 A three phase on S500 and R500.[1][2][3][4][5]
Device response: output shuts down; cycle power to clear
Likely causes
- Weld procedure asking for more average current than the machine can deliver
- Duty cycle too high for the procedure
- Possible short in the output (weld) circuit
First checks, in this order
- Adjust the procedure or reduce the load to lower the current drawn from the machine.
- Check the output circuit, cables and torch for a short.
- Cycle power to clear. If the error keeps coming back, contact a Lincoln authorized field service facility.
54: Secondary (output) over current
Hits OEE: AvailabilityWhat it means: The long term average weld current has gone over the i400 limit of 450 A, and the machine turns its output off immediately.[8][14]
Also on: FANUC robot controller: LECO (FANUC#) 84
Device response: output off immediately; cycle power to clear
Likely causes
- Weld procedure demanding more than 450 A average
- Duty cycle too high for the procedure
First checks, in this order
- Adjust the procedure to reduce output demand.
- Cycle power to clear the code.
31: Primary overcurrent error
Hits OEE: AvailabilityWhat it means: Too much current on the primary (input) side of the inverter, so the machine will not give output.[6][7][9][12]
Device response: output off; cycle power to clear
Likely causes
- Short in the main transformer or output rectifier (455M, 455M/STT)
- Switch board or output rectifier failure (455/R)
- Short in the output circuit
First checks, in this order
- Turn the machine off and remove all loads from the output.
- Turn it back on. If the error comes back, turn power off and contact a Lincoln authorized field service facility.
31: Primary (Input) overcurrent error
Hits OEE: AvailabilityWhat it means: Too much primary (input) current; the main contactor drops out when output is started.[8][14]
Also on: FANUC robot controller: LECO (FANUC#) 49
Device response: output off; cycle power to clear
Likely causes
- Switch board failure
- Output rectifier failure
- Short in the output circuit
First checks, in this order
- Turn the machine off and remove all loads from the output.
- Turn it back on and activate the output.
- If the error comes back, turn power off and contact a Lincoln authorized field service facility.
41: Secondary overcurrent error
Warning: act before it becomes a stopWhat it means: The weld current limit has been exceeded and the machine phases its output back to about 100 A, which welders call noodle welding. The limit is 570 A on the standard stud and 325 A on single phase input (and on the STT stud of the 455/R).[6][7][9][12]
Device response: output phases back to about 100 A
Likely causes
- Procedure drawing too much current, often a high wire feed speed procedure
- Single phase input (loss of L2), which lowers the limit from 570 A to 325 A
First checks, in this order
- Adjust the procedure or reduce the load to lower the current drawn.
- Check that all three input phases are present.
- If the problem persists, contact a Lincoln authorized field service facility.
49: Single phase error
Warning: act before it becomes a stopWhat it means: The machine is running on single phase input power; the weld current limit drops from 570 A to 325 A, so it will not produce full output.[6][7][9][12]
Device response: keeps running with the weld current limit cut to 325 A
Likely causes
- Loss of the middle input leg (L2)
- Blown fuse, open breaker or loose connection on one input line
First checks, in this order
- Measure the input voltage on all three lines and compare it with the rating plate on the rear of the machine.
- Check the input fuses or breaker and the L2 connection at the disconnect and at the machine.
58: Primary Fault error
Hits OEE: AvailabilityWhat it means: The main control board reports a fault on the primary (input) side, most likely an over power condition that pulled the primary bus voltage too low. The input control board holds the detailed code.[1][2][3][4][5]
Device response: output off; cycle power to clear
Likely causes
- Over power condition causing undervoltage on the primary bus
- An input control board fault (see the 3xx codes)
First checks, in this order
- Read the input control board code from its status light or status beeper (on the R350 the light is inside, seen through the left case side louvers).
- Cycle input power.
- If the error does not clear, contact the Lincoln Service Department.
336: Thermal Fault
Hits OEE: AvailabilityWhat it means: Input control board code: the thermostat on the primary module has tripped.[1][2][3][4][5][13]
Also on: S350 machine schematic PFC board legend: THERMAL FAULT (NO FIRST STAGE FAN)
Device response: S500 and R500: Temporary, clears by itself when the condition is gone
Likely causes
- Bottom (first stage) fan not working
- Fan malfunction or blocked air vent (S500, R500)
First checks, in this order
- Check that the bottom fan runs.
- Clear blocked vents and louvers and let the machine cool.
- On S500 and R500 this code is Temporary and clears by itself once the condition is removed.
81: Motor Overload
Hits OEE: AvailabilityWhat it means: Wire drive module code: the long term average wire drive motor current limit has been exceeded, which usually means the wire feed system is mechanically overloaded.[2][4][5][8]
Also on: i400 on a FANUC robot: LECO (FANUC#) 129
Likely causes
- Mechanical overload of the wire feed system
- Conduit to the feeder with bends or twists, or too long
- Gear ratio with too little torque for the wire size
First checks, in this order
- Check for wire feeding problems along the whole path from reel to torch.
- Remove bends and twists in the conduit, and use a shorter conduit from the reel if it is long.
- If the problem continues, use a higher torque gear ratio (lower speed range).
82: Motor Overcurrent
Hits OEE: AvailabilityWhat it means: Wire drive module code: the absolute maximum motor current has been exceeded. This is a short term limit that protects the drive circuitry.[2][4][5][8]
Also on: i400 on a FANUC robot: LECO (FANUC#) 130
Likely causes
- Wire drive jammed or seized for a moment
- Sudden mechanical load on the feed rolls or motor
First checks, in this order
- Check the drive rolls, gears and wire path for a jam.
- Check for feeding problems and conduit bends.
- Cycle power to clear; if it repeats, contact a Lincoln authorized field service facility.
83: Shutdown #1 Is Open
Hits OEE: AvailabilityWhat it means: Wire drive module code: the Shutdown 1 input on the green I/O connector on the bottom of the controller is open, so the wire drive stops.[2][5]
Likely causes
- Jumper missing or connector loose on the green I/O connector
- Remote shutdown circuit open (safety device, door switch or cell interlock wired to Shutdown 1)
First checks, in this order
- If the input is not used externally, check the green I/O connector and its jumper.
- If a remote circuit uses the input, check that circuit end to end.
84: Shutdown #2 Is Open
Hits OEE: AvailabilityWhat it means: Wire drive module code: the Shutdown 2 input on the green I/O connector on the bottom of the controller is open, so the wire drive stops.[2][5]
Likely causes
- Jumper missing or connector loose on the green I/O connector
- Remote shutdown circuit open (safety device or cell interlock wired to Shutdown 2)
First checks, in this order
- If the input is not used externally, check the green I/O connector and its jumper.
- If a remote circuit uses the input, check that circuit end to end.
83: Shutdown #1
Hits OEE: AvailabilityWhat it means: Wire drive module code. The shutdown inputs are disabled on these models, so this code means the feed head control board may have the wrong operating software.[4][8][14]
Also on: i400 on a FANUC robot: LECO (FANUC#) 131
Likely causes
- Wrong operating software on the feed head control PC board
First checks, in this order
- Note the code and have the feed head control board software checked and reloaded by Lincoln service.
84: Shutdown #2
Hits OEE: AvailabilityWhat it means: Wire drive module code. The shutdown inputs are disabled on these models, so this code means the feed head control board may have the wrong operating software.[4][8][14]
Also on: i400 on a FANUC robot: LECO (FANUC#) 132
Likely causes
- Wrong operating software on the feed head control PC board
First checks, in this order
- Note the code and have the feed head control board software checked and reloaded by Lincoln service.
32: Capacitor "A" under voltage (Left side facing machine)
Hits OEE: AvailabilityWhat it means: Low voltage on main capacitor bank A, the left one when you face the machine.[6][7][9][12]
Device response: output off; cycle power to clear
Likely causes
- Wrong input voltage configuration (reconnect)
- With an overvoltage code on the same side (34): zero voltage on that side's capacitors, usually from an open or short in the primary side
First checks, in this order
- Power down and check the input voltage reconnect against the diagram on the reconnect cover.
- Check that the input voltage matches the rating plate.
- If 32 and 34 appear together, contact a Lincoln authorized field service facility for the primary side repair.
33: Capacitor "B" under voltage (Right side facing machine)
Hits OEE: AvailabilityWhat it means: Low voltage on main capacitor bank B, the right one when you face the machine. Together with an overvoltage code on the same side (35) it means zero voltage on that side's capacitors.[6][7][9][12]
Device response: output off; cycle power to clear
Likely causes
- Wrong input voltage configuration (reconnect)
- Open or short in the primary side of the machine
First checks, in this order
- Power down and check the input voltage reconnect against the diagram on the reconnect cover.
- Check that the input voltage matches the rating plate.
- If 33 and 35 appear together, contact a Lincoln authorized field service facility for the primary side repair.
34: Capacitor "A" over voltage (Left side facing machine)
Hits OEE: AvailabilityWhat it means: Too much voltage on main capacitor bank A, the left one when you face the machine.[6][7][9][12]
Device response: output off; cycle power to clear
Likely causes
- Wrong input voltage configuration (reconnect)
- With an undervoltage code on the same side (32): zero voltage on that side's capacitors, usually from an open or short in the primary side
First checks, in this order
- Power down and check the input voltage reconnect against the diagram on the reconnect cover.
- Check that the line voltage matches the rating plate.
- If 34 and 32 appear together, contact a Lincoln authorized field service facility.
35: Capacitor "B" over voltage (Right side facing machine)
Hits OEE: AvailabilityWhat it means: Too much voltage on main capacitor bank B, the right one when you face the machine. Together with an undervoltage code on the same side (33) it means zero voltage on that side's capacitors.[6][7][9][12]
Device response: output off; cycle power to clear
Likely causes
- Wrong input voltage configuration (reconnect)
- Open or short in the primary side of the machine
First checks, in this order
- Power down and check the input voltage reconnect against the diagram on the reconnect cover.
- Check that the line voltage matches the rating plate.
- If 35 and 33 appear together, contact a Lincoln authorized field service facility.
37: Soft start error
Hits OEE: AvailabilityWhat it means: The main capacitor precharge failed at power up; it usually comes with codes 32 to 35.[6][7][9][12]
Device response: output off; cycle power to clear
Likely causes
- Capacitor precharge circuit failure
- Input configuration or primary side problem behind the 32 to 35 codes that come with it
First checks, in this order
- Read all codes on the status light; work on the 32 to 35 codes first.
- Check the input voltage reconnect and the line voltage.
- Cycle power; if 37 returns, contact a Lincoln authorized field service facility.
43: Capacitor delta error
Hits OEE: AvailabilityWhat it means: The voltage difference between the two main capacitor banks is larger than allowed; it may come with codes 32 to 35.[6][7][9][12]
Device response: output off; cycle power to clear
Likely causes
- Capacitor banks out of balance
- Primary side problem behind the 32 to 35 codes that come with it
First checks, in this order
- Read all codes on the status light and handle the 32 to 35 codes as well.
- Check the input voltage reconnect and the line voltage.
- If the error stays after a power cycle, contact a Lincoln authorized field service facility.
56: Chopper communication error
Hits OEE: AvailabilityWhat it means: The communication link between the main control board and the chopper has errors.[1][2][3][4][5]
Device response: output off; cycle power to clear
Likely causes
- Communication errors on the internal link between the main control board and the chopper
First checks, in this order
- Cycle input power to the machine.
- If the error does not clear, contact the Lincoln Service Department.
71: Secondary (Output) over power error
Hits OEE: AvailabilityWhat it means: The long term weld (secondary) power limit has been exceeded: 25 kW on three phase input, 14 kW on single phase input.[2][3][5]
Device response: output off; cycle power to clear
Likely causes
- Procedure running high current and voltage for long periods
- Machine on single phase input, which lowers the limit to 14 kW
First checks, in this order
- Reduce the output demand of the procedure or the duty cycle.
- Confirm all three input phases are present if the machine should be on three phase.
- Cycle power to clear.
331: Peak input current limit
Hits OEE: AvailabilityWhat it means: Input control board code: the input current limit has been exceeded, typically a short term power overload.[1][4][13]
Also on: S350 machine schematic PFC board legend: PEAK INPUT CURRENT LIMIT
Likely causes
- Short term power overload from the weld procedure
- Input supply problem
First checks, in this order
- Reduce the output demand and cycle power.
- If the problem persists, contact the Lincoln Service Department.
331: Instantaneous Input Current Limit
Hits OEE: AvailabilityWhat it means: Input control board code: the instantaneous input current limit has been exceeded, typically a short term power overload.[2][3][5]
Device response: Persistent: cycle power to clear
Likely causes
- Short term power overload from the weld procedure
First checks, in this order
- Cycle power to clear (Persistent code).
- If the problem persists, contact the Lincoln Service Department.
337: Pre-charge timeout
Hits OEE: AvailabilityWhat it means: Input control board code: the start-up sequence failed because the DC bus did not charge to the required level by the end of precharge.[1][2][3][4][5]
Also on: S500 and R500 manuals write it as Precharge Timeout
Device response: S500 and R500: Persistent, cycle power to clear
Likely causes
- Problem in the start-up (precharge) sequence
- Low or unstable input voltage at power up
First checks, in this order
- Check the input voltage, then cycle power (Persistent code on S500 and R500).
- If the problem persists, contact the Lincoln Service Department.
346: Transformer primary over current
Hits OEE: AvailabilityWhat it means: Input control board code: the transformer primary current is too high, typically a short term power overload.[1][2][3][4][5]
Device response: S500 and R500: Persistent, cycle power to clear
Likely causes
- Short term power overload from the weld procedure
First checks, in this order
- Reduce the output demand and cycle power (Persistent code on S500 and R500).
- If the problem persists, contact the Lincoln Service Department.
333: Under-voltage lockout
Hits OEE: AvailabilityWhat it means: Input control board code: the +15 V DC supply on the input control board is too low.[1][4]
Likely causes
- Input voltage outside the acceptable range
- Input control board supply problem
First checks, in this order
- Verify the input voltage is within the acceptable range on the rating plate.
- If the problem persists, contact the Lincoln Service Department.
334: Startup Current Check Failure
Hits OEE: AvailabilityWhat it means: Input control board code: the input current limit was exceeded while the machine was powering up.[2][3][5][13]
Also on: S350 machine schematic PFC board legend: START UP CURRENT CHECK FAILURE
Device response: Persistent: cycle power to clear
Likely causes
- Input current too high during power up
First checks, in this order
- Cycle power to clear (Persistent code).
- If the problem persists, contact the Lincoln Service Department.
335: Startup Voltage Check Failure
Hits OEE: AvailabilityWhat it means: Input control board code: the input voltage was too high or too low while the machine was powering up.[2][3][5][13]
Also on: S350 machine schematic PFC board legend: START UP VOLTAGE CHECK FAILURE
Device response: Temporary: clears by itself when the condition is gone
Likely causes
- Input voltage outside 200 V to 650 V at power up
First checks, in this order
- Verify that the input voltage is between 200 V and 650 V.
- This code is Temporary and clears by itself once the voltage is back in range.
338: Input Power Limit
Hits OEE: AvailabilityWhat it means: Input control board code: the input power drawn by the machine went above a safe level.[2][3][5]
Device response: Persistent: cycle power to clear
Likely causes
- Weld procedure drawing too much input power
First checks, in this order
- Reduce the output demand and cycle power (Persistent code).
- If the problem persists, contact the Lincoln Service Department.
341: Input Voltage Dropout
Hits OEE: AvailabilityWhat it means: Input control board code: the input voltage dropped out for a moment.[2][3][5]
Device response: Temporary: clears by itself when the condition is gone
Likely causes
- Loose input connection
- Poor quality or sagging input power
First checks, in this order
- Check the input connections.
- Verify the quality of the input power.
- This code is Temporary and clears by itself once the voltage is stable.
347: Average Input Current Limit
Hits OEE: AvailabilityWhat it means: Input control board code: the average input current limit has been exceeded, typically a short term power overload.[2][3][5]
Device response: Persistent: cycle power to clear
Likely causes
- Short term power overload from the weld procedure
First checks, in this order
- Reduce the output demand and cycle power (Persistent code).
- If the problem persists, contact the Lincoln Service Department.
349: Bus Undervoltage
Hits OEE: AvailabilityWhat it means: Input control board code: the DC bus voltage dropped below the allowed limit.[2][3][5]
Device response: Temporary: clears by itself when the condition is gone
Likely causes
- Low or sagging input voltage
- Input power problem during heavy output
First checks, in this order
- Check the input voltage and connections.
- This code is Temporary and clears by itself once the condition is gone.
- If the problem persists, contact the Lincoln Service Department.
11: CAN communication bus off
Hits OEE: AvailabilityWhat it means: The CAN communication bus between the power source and the feeder or user interface has shut down, probably after too many communication errors.[6][7][9][12]
Device response: output off; cycle power to clear
Likely causes
- Excessive number of communication errors on the bus
- Damaged or loose control cable or communication leads
First checks, in this order
- Note the code before switching off.
- Check the control cable and its connectors between the power source and the wire feeder.
- Cycle power to reset.
12: User Interface time out error
Hits OEE: AvailabilityWhat it means: The user interface has stopped responding to the power source.[6][7][9][12]
Device response: output off; cycle power to clear
Likely causes
- Fault or bad connection in the communication leads
- Damaged control cable
First checks, in this order
- Check the communication leads and control cable from the power source to the user interface.
- Cycle power to reset.
21: Unprogrammed Weld Mode
Hits OEE: AvailabilityWhat it means: The selected weld mode is not programmed in the power source welding software.[6][7][9][12]
Likely causes
- Weld mode selected that is missing from the loaded welding software
First checks, in this order
- Check the weld mode selected on the feeder or robot.
- Contact the Lincoln Service Department for instructions on reloading the welding software.
22: Empty Weld Table
Hits OEE: AvailabilityWhat it means: The weld table in the power source is empty, so it cannot run a weld mode.[6][7][9][12]
Likely causes
- Welding software (weld table) missing or not loaded
First checks, in this order
- Contact the Lincoln Service Department for instructions on reloading the welding software.
23: Weld Table checksum error
Hits OEE: AvailabilityWhat it means: The weld table failed its checksum test, so the welding software is corrupt.[6][7][9][12]
Likely causes
- Corrupted welding software
First checks, in this order
- Contact the Lincoln Service Department for instructions on reloading the welding software.
32: Capacitor "A" under voltage (right side facing the Switch PC Board)
Hits OEE: AvailabilityWhat it means: Low voltage on main capacitor A, the right one when you face the switch PC board.[8][14]
Also on: FANUC robot controller: LECO (FANUC#) 50
Device response: output off; cycle power to clear
Likely causes
- Wrong input voltage configuration (reconnect)
- Open or short circuit in the primary side of the machine
First checks, in this order
- Power down and check the input voltage reconnect against the diagram on the reconnect cover.
- Check that the input voltage matches the rating plate.
- If the code returns, contact a Lincoln authorized field service facility.
33: Capacitor bank "B" under voltage (left side facing the Switch PC Board)
Hits OEE: AvailabilityWhat it means: Low voltage on main capacitor bank B, the left one when you face the switch PC board.[8][14]
Also on: FANUC robot controller: LECO (FANUC#) 51
Device response: output off; cycle power to clear
Likely causes
- Wrong input voltage configuration (reconnect)
- Open or short circuit in the primary side of the machine
First checks, in this order
- Power down and check the input voltage reconnect against the diagram on the reconnect cover.
- Check that the input voltage matches the rating plate.
- If the code returns, contact a Lincoln authorized field service facility.
34: Capacitor "A" over voltage (right side facing the Switch PC Board)
Hits OEE: AvailabilityWhat it means: Too much voltage on main capacitor A, the right one when you face the switch PC board.[8][14]
Also on: FANUC robot controller: LECO (FANUC#) 52
Device response: output off; cycle power to clear
Likely causes
- Wrong input voltage configuration (reconnect)
- Line voltage too high
- Capacitors out of balance (see code 43)
First checks, in this order
- Power down and check the input voltage reconnect.
- Measure the line voltage against the rating plate.
- Check for code 43 alongside it.
35: Capacitor "B" over voltage (left side facing the Switch PC Board)
Hits OEE: AvailabilityWhat it means: Too much voltage on main capacitor B, the left one when you face the switch PC board.[8][14]
Also on: FANUC robot controller: LECO (FANUC#) 53
Device response: output off; cycle power to clear
Likely causes
- Wrong input voltage configuration (reconnect)
- Line voltage too high
- Capacitors out of balance (see code 43)
First checks, in this order
- Power down and check the input voltage reconnect.
- Measure the line voltage against the rating plate.
- Check for code 43 alongside it.
37: Softstart (pre-charge) error
Hits OEE: AvailabilityWhat it means: The main capacitor precharge failed at power up; it usually comes with codes 32 and 33.[8][14]
Also on: FANUC robot controller: LECO (FANUC#) 55
Device response: output off; cycle power to clear
Likely causes
- Capacitor precharge circuit failure
- Input configuration or primary side problem behind codes 32 and 33
First checks, in this order
- Read all codes on the status light and work on 32 and 33 first.
- Check the input voltage reconnect and the line voltage.
- If 37 returns after a power cycle, contact a Lincoln authorized field service facility.
39: Misc. hardware fault
Hits OEE: AvailabilityWhat it means: An unknown glitch has occurred on the fault interrupt circuitry.[8][10][14]
Also on: Power Wave STT Module (same code and name). i400 on a FANUC robot: LECO (FANUC#) 57.
Device response: output off; cycle power to clear
Likely causes
- Primary overcurrent event (i400)
- Intermittent connections in the thermostat circuit
First checks, in this order
- Check the thermostat circuit wiring and connectors for loose or intermittent contacts.
- Check for a primary overcurrent (code 31) alongside it.
- Cycle power; if it repeats, contact a Lincoln authorized field service facility.
43: Capacitor delta error
Hits OEE: AvailabilityWhat it means: The voltage difference between the main capacitors is larger than allowed; it may come with codes 32 to 35.[8][14]
Also on: FANUC robot controller: LECO (FANUC#) 67
Device response: output off; cycle power to clear
Likely causes
- Open or short in the primary circuit
- Open or short in the secondary circuit
First checks, in this order
- Read all codes on the status light and handle the 32 to 35 codes as well.
- Check the input voltage reconnect and the line voltage.
- If the error stays after a power cycle, contact a Lincoln authorized field service facility.
99: STT Status error
Hits OEE: AvailabilityWhat it means: The STT switch PC board in the Power Wave STT Module reports a status failure.[10]
Device response: output off; cycle power to clear
Likely causes
- Weld leads connected wrongly (reverse polarity)
- Loss of input voltage to the STT switch board
- STT switch board failure
First checks, in this order
- Check the weld cable connections and polarity.
- Look at the diagnostic LEDs on the STT switch PC board: gate and status LEDs off while triggered usually means reversed weld cables; status LED off all the time points to the board's power supply undervoltage lockout, so verify the input voltage to the board.
- Cycle power to clear.
Log it, or the same alarm comes back
A power source error stops the weld, and in a robot cell it stops the cell, so in OEE terms it is a breakdown. Log the code, the cell and the minutes lost, and the parts scrapped by a weld cut short, which count against quality.
- Reason code: the code plus the cell, for example Power Wave 36 thermal, weld cell 4, so a thermal error that trips every afternoon shift shows up as a pattern.
- Loss bucket: a stop that needs a reset, a part or a technician is an availability loss (breakdown). Stops shorter than your micro-stop threshold go to performance (minor stops). The six big losses page shows where each one belongs.
- What to count: how often each code fires per week and the minutes it costs. Two numbers a week turn "that alarm comes up sometimes" into a ranked list. The MTBF and MTTR calculator and the downtime cost calculator do the math.
The free OEE tracker logs each stop with its reason and turns the week into a downtime Pareto, so the code that costs the most rises to the top.
fabrico.io has a MIG welder troubleshooting guide. A code tells you what the device detected, not what happened at the machine in the seconds before. Fabrico's camera-based OEE software syncs camera video with machine data, so you can replay the moment the cell stopped next to the welder's error.
Frequently asked questions
What does error 31 mean on a Lincoln Power Wave?
Code 31 is a primary overcurrent error: too much current on the input side of the inverter. On the 455M and 455M/STT Lincoln points to a short in the main transformer or output rectifier, on the 455/R and i400 to a switch board or output rectifier failure. Turn the machine off, remove all loads from the output, turn it back on and try the output again. If 31 comes back, power down and call a Lincoln authorized field service facility. On an i400 connected to a FANUC robot the same fault shows as LECO 49.
How do I read the status LED error code on a Power Wave S350?
Look at the status light on the case front before you switch anything off. Steady green is normal. Alternating red and green means a fault: count the red flashes for each digit, with a long pause between digits, and a green flash separating one code from the next. Only active codes show on the light. The input control board flashes its own three digit codes that start with 3, such as 331 or 336. Lincoln's Diagnostics Utility from powerwavesoftware.com is the preferred way to read codes because it also shows the error log history.
How do I clear an error on a Lincoln Power Wave?
Fix the cause first, then turn the power source off and back on; that clears the active error. On S500 and R500 input board codes, Persistent codes (for example 331, 334, 337, 346) need that power cycle, while Temporary codes (335, 336, 341, 349) clear by themselves once the condition is gone. Main control board codes with three or four digits are fatal internal errors: if a power cycle does not clear them, contact Lincoln service (on the 455M, Lincoln suggests reloading the operating system and then replacing the control board).
What does error 36 thermal mean on a Power Wave?
Code 36 is a thermal error: the machine is too hot and stops output, usually with the yellow Thermal LED lit. Check that the fans run, clear blocked louvers and dirty cooling channels, and make sure the procedure stays within the duty cycle. If it persists, check the thermostat circuit for broken wires or a failed thermostat. Lincoln also issued service notice 201408004-3 for some 2014 S500, S500 CE and R500 units whose Rev 2 fans can stall and cause error 36.
Why does my Power Wave 455M weld at about 100 amps after error 41?
Code 41 means the secondary (weld) current limit was exceeded, so the machine phases back to about 100 A to protect itself, which welders call noodle welding. The limit is 570 A on the standard stud and 325 A on single phase input, so also look for code 49 (single phase, usually a lost L2 leg). Lower the procedure's current demand, often the wire feed speed, and check all three input phases.
Sources
Codes and meanings follow the manufacturer documentation below. Wording is ours, simplified for the shop floor; the manual for your exact model and software version wins if it differs.
- Power Wave S350+, S350 and S350 Aluminum Instruction Manual, IM10061-G, issue date Sept 2026, code numbers 11694 to 14102, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave S500+ and S500 Instruction Manual, IM10456-D, issue date Sept 2026, code numbers 12772 to 14105, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave S500 Operator's Manual, IM10118-A, issue date Oct 2014, code numbers 11813 and 12243, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave R350 Operator's Manual, IM10083-A, issue date Feb 2019, code number 11745, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave R500 Operator's Manual, IM10295, issue date Feb 2019, code number 12483, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave 455M Operator's Manual, IM762-E, issue date Jan 2013, code numbers 10942 to 11943, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave 455M/STT Operator's Manual, IM10301, issue date July 2015, code number 12507, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave i400 Operator's Manual, IM10465, issue date Feb 2018, code number 12800, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave 455/R Operator's Manual, IM690-A, Feb 2019, code numbers 10675 and 10676, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave STT Module machine schematic G6862-1 with the page Troubleshooting the Power Wave STT Module (undated), hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Lincoln Electric Service Notice 201408004-3, M22853 Rev 2 Fan Replacement, Power Wave S500, S500 CE and R500, dated August 27, 2014, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave 455M Operator's Manual, IM10302, issue date July 2015, code number 12506, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave S350 Machine Schematic, Rev A (marked for reference only), hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
- Power Wave i400 Operator's Manual, IM943-A, issue date Jun 2016, code numbers 11454, 11454R and 11774, hosted by Lincoln Electric (ch-delivery.lincolnelectric.com)
See the moment the cell stopped
Fabrico, a light MES with computer vision, syncs camera footage with machine and timeline data, so you can replay the exact moment the cell stopped and review the cause next to the welder's error. Cameras also catch short stops and a line that is switched on but not producing, the losses nobody writes down. Machines connect through a PLC, a Fabrico IoT device or an AI camera.
Book a Fabrico demoRelated: welding troubleshooting · spot welder · ABB robot error codes · FANUC robot SRVO alarms · industrial robot troubleshooting
Other alarm code lookups: FANUC: servo amplifier · spindle amplifier · robot SRVO | Siemens: MICROMASTER 440 · MASTERDRIVES · SINAMICS G120 · SINAMICS V90 servo · SINAMICS V20 | ABB: ACS550 drive · ACS800 drive · robot IRC5 | Okuma: OSP alarms | Haas: alarm lookup | Mitsubishi: MELSERVO servo · FR-D700 and FR-E700 inverters · FX PLC | Allen-Bradley: Kinetix and Ultra3000 · MicroLogix · PowerFlex 753 and 755 · PowerFlex 70 and 700 · 1336 and 1305 | Yaskawa: V1000 drive · SERVOPACK servo · Motoman robot | Delta: VFD drives · ASDA servo | Eaton: DC1 and SVX9000 drives | Control Techniques: Commander SK and M200 | Kollmorgen: AKD servo | Lenze: SMVector, 8200, 8400, i500 | Magnetek: IMPULSE and DSD 412 | Omron: MX2 and RX inverters · G5 and 1S servo · CP1 and CJ2 PLC | WEG: CFW500, CFW300, CFW11, CFW08 | Hitachi: WJ200 inverter | Toshiba: E3, Q9, P9, S15, nC3, AS3 | AutomationDirect: GS10, GS20, GS4, GS1 to GS3 | Pilz: PNOZ safety relays | SICK: S3000, S300, microScan3 | SANYO DENKI: SANMOTION servo | Parker: SSD 590+, 690+, AC10 | KEB: COMBIVERT F5 | Epson: robot RC700, RC90 | B&R: ACOPOS servo | Schneider Electric: Lexium 32 servo | Bosch Rexroth: IndraDrive | Vacon: NX, VACON 100 and 20 | Fuji Electric: FRENIC-Mini, Multi, Ace, MEGA | LS Electric: S100, G100, iG5A | Panasonic: MINAS A6 and A5 servo | Invertek: Optidrive E3, P2, Eco | SEW-Eurodrive: MOVITRAC B and MOVIDRIVE B
Related tools: full troubleshooting directory · OEE calculator · downtime cost · MTBF / MTTR · glossary