Magnetek Drive Fault Codes
The fault and alarm codes of Magnetek IMPULSE crane and hoist drives (G+ and VG+ Series 4, G+ Mini) and the DSD 412 DC drive: what each one means, the likely causes, the first checks with the parameters to look at, and how to log it so it stops coming back.
How faults and alarms show
DSD 412: the Standard Control/Display Unit (SCDU) on the Drive Control PCB lights its red FAULT LED and shows F plus the fault number, for example F904. Function #0 is the Fault List: the first 16 faults since the last reset or power-up, erased at power down.
Function #800 is the Error List: the 16 most recent errors, kept in battery-backed NVRAM. Function #801 sets whether each code goes to the Fault List, the Error List, both or neither.
Reset with the DRIVE RESET button (S1) on the power cube cover (it does nothing while the drive is enabled), with the car controller's fault reset input at A1TB1-49, or by automatic reset (Function #101). IMPULSE G+/VG+ Series 4: the LCD keypad (five 16-character lines) shows the code and its name, for example OC Over Current.
A fault sets the brake, flashes the operation lights and switches fault relay MB-MC; an alarm flashes the ALM LED while the drive keeps running. U02-01 to U02-28 show the conditions at the last fault, U03-01 to U03-10 list the 10 most recent faults and U03-11 onward their elapsed times. Reset with the RESET key, a digital input set to Fault Reset (H01-xx = 3F), or a power cycle.
IMPULSE G+ Mini: LED keypad. A major fault shows the code with the ALM LED lit steady; a minor fault or an alarm flashes the code and the ALM LED. U02 is the fault trace, U03.01 to U03.10 the 10 most recent faults, U03.11 to U03.20 their elapsed times.
Reset with the RESET key, a digital input set to Fault Reset (3F), or a power cycle; a flashing minor fault clears at the next run command.
After switching off, wait until the red CHARGE LED is out, then wait at least 5 minutes (G+/VG+ Series 4) or 10 minutes (G+ Mini) and measure the DC bus voltage to confirm it is safe. Do not run a withstand (hipot) voltage test on any part of the drive.
Hoists: after a BE2, BE6 or BE8 brake fault or alarm, do not switch the power off; move the load to a safe spot and lower it before working on the brake. Stop using the hoist after a speed deviation (DEV) or encoder (PGO) fault until the cause is found, because continued running can lose control of the load. Sources: DSD 412 manual CS00407 rev 12, pages 18 and 94.
IMPULSE G+/VG+ Series 4 Technical Manual 144-23910 R8, page 8 and pages 204 to 209. Series 4 Quick Start Guide 144-27514 R1. IMPULSE G+ Mini Technical Manual 144-25085 R8, page 8. Follow lockout/tagout and your site's safe-work procedures, and check the manual for your exact model before you act.
Quick lookup
Faults stop the drive and the machine it moves, so in OEE they are availability losses; alarms let the drive keep running until you act.
Type a code or a word (overcurrent, overvoltage, brake, encoder) to filter the list. Click a code for its causes and first checks.
73 codes
| Code | Drive | Name |
|---|---|---|
| OC | IMPULSE Series 4 | Over Current |
| SC | IMPULSE Series 4 | Short Circuit |
| F901 | DSD 412 | PCU IST FAULT |
| GF | IMPULSE Series 4 | Ground Fault |
| GF | IMPULSE G+ Mini | Ground Fault |
| OV | IMPULSE Series 4 | DC Bus Overvolt |
| oV | IMPULSE G+ Mini | DC Bus Overvolt |
| F408 | DSD 412 | EXCESSIVE PCU CEMF FAULT |
| UV1 | IMPULSE Series 4 | DC Bus Undervolt |
| UV | IMPULSE Series 4 | DC Bus Undervolt |
| Uv1 | IMPULSE G+ Mini | DC Bus Undervolt |
| Uv | IMPULSE G+ Mini | DC Bus Undervolt |
| F904 | DSD 412 | LOW LINE FAULT |
| F406 | DSD 412 | 10% LOW LINE ALARM |
| F903 | DSD 412 | LINE SYNC FAILURE |
| UV2 | IMPULSE Series 4 | CTL PS Undervolt |
| UV3 | IMPULSE Series 4 | MC Answerback |
| F902 | DSD 412 | POWER SUPPLY FAULT |
| OH | IMPULSE Series 4 | Heatsnk Over temp |
| OH1 | IMPULSE Series 4 | Heatsink MaxTemp |
| F908 | DSD 412 | OVER TEMPERATURE |
| FAn | IMPULSE Series 4 | Cooling FAN Err |
| OL1 | IMPULSE Series 4 | Motor Overloaded |
| OL2 | IMPULSE Series 4 | VFD Overloaded |
| F400 | DSD 412 | MOTOR OVERLOAD |
| OH3 | IMPULSE Series 4 | Motor Overheat 1 |
| oL8 | IMPULSE G+ Mini | Klixon |
| F941 | DSD 412 | MOTOR THERMOSTAT OPEN |
| PF | IMPULSE Series 4 | Input Phase Loss |
| F910 | DSD 412 | BLOWN FUSE |
| LF | IMPULSE Series 4 | Output Phase Loss |
| F404 | DSD 412 | OPEN ARMATURE CIRCUIT FAULT |
| PGO-1-S / PGO-1-H | IMPULSE Series 4 | PG Open Ch1 |
| DEV | IMPULSE Series 4 | Speed Deviation |
| OS | IMPULSE Series 4 | Over Speed |
| F97 | DSD 412 | OVERSPEED TRIP |
| F98 | DSD 412 | TACH/ENCODER LOSS |
| F99 | DSD 412 | REVERSE TACH/ENCODER |
| F410 | DSD 412 | SPEED ERROR FAULT |
| BE1 | IMPULSE Series 4 | Rollback Detect |
| BE2 | IMPULSE Series 4 | No Current |
| BE3 | IMPULSE Series 4 | Brake Release NG |
| BE4 | IMPULSE Series 4 | Brake Answer 1 |
| BE5 | IMPULSE Series 4 | Brake Answer 2 |
| BE6 | IMPULSE Series 4 | Brake Slipping |
| BE7 | IMPULSE Series 4 | Brake Welded |
| BE8 | IMPULSE Series 4 | Brake Slipping |
| BE0 | IMPULSE Series 4 | Brake Ans Lost |
| DIR | IMPULSE Series 4 | Direction Fault |
| SNAP | IMPULSE Series 4 | Snapped Shaft |
| F402 | DSD 412 | CONTACTOR FAULT |
| F900 | DSD 412 | PCU LOOP FAULT |
| F405 | DSD 412 | SAFETY CIRCUIT FAULT |
| CE | IMPULSE Series 4 | Serial Com Err |
| F117 | DSD 412 | 10 SEC COMM. START FAULT |
| F118 | DSD 412 | 150 MSEC COMM. MSG FAULT |
| RR | IMPULSE Series 4 | DynBrk Transistr |
| F401 | DSD 412 | EXCESSIVE FIELD CURRENT |
| F905 | DSD 412 | FIELD LOSS |
| F403 | DSD 412 | 5-MIN FULL FIELD FAULT |
| F407 | DSD 412 | EXCESSIVE DCU CEMF ALARM |
| F909 | DSD 412 | EXCESSIVE RIPPLE |
| F911 | DSD 412 | SHORTED SCR |
| F411 | DSD 412 | MAX AUTO-RESETS ATTEMPTED |
| F926 | DSD 412 | PCU WATCHDOG TIMEOUT FAULT |
| Prot | DSD 412 | CORRUPTED NV RAM DATA |
| CPF06 | IMPULSE Series 4 | EEPROM Error |
| HBB / HBBf | IMPULSE Series 4 | Hardware Base Block |
| BB | IMPULSE Series 4 | Base Block |
| EF1 to EF8 | IMPULSE Series 4 | External Fault 1 to External Fault 8 |
| CF | IMPULSE G+ Mini | Control Fault |
| CRST | IMPULSE G+ Mini | Cannot reset |
| dnE | IMPULSE G+ Mini | Drive not ready |
Each code: causes and first checks
OC: Over Current
Hits OEE: AvailabilityWhat it means: Output current went above 200% of the drive's rated output current.[3][5]
Also on: IMPULSE G+ Mini: same fault shown as oC (Over Current), same 200% trip level.
Likely causes
- Phase-to-phase short in the motor or motor wiring
- Acceleration or deceleration time too short
- Torque limits (C07-01 to C07-04) raised too high
- Erratic or missing encoder feedback, so the drive pushes more current trying to hold position
First checks, in this order
- Check the motor and motor leads for a phase-to-phase short with an insulation tester (megohmmeter).
- Extend the acceleration and deceleration times.
- Check the torque limit settings C07-01 to C07-04.
- On encoder drives, check the pulse wheel or shaft coupling alignment and the encoder cable for breaks, shorts and a poorly grounded shield.
SC: Short Circuit
Hits OEE: AvailabilityWhat it means: The drive detected a short circuit on its output.[3]
Likely causes
- Shorted motor winding
- Short in the motor cable or at the terminals
First checks, in this order
- Disconnect the motor from the drive.
- Check the motor and the motor cable for a short with an insulation tester.
F901: PCU IST FAULT
Hits OEE: AvailabilityWhat it means: Armature current went above 300% of rated armature current (instantaneous overcurrent trip).[1][2]
Likely causes
- Ground fault or intermittent connection in the motor armature circuit
- Faulty current measuring module
- Poor current regulator tuning
- Bad SCR gating (Magnetek application note 103 says this usually shows up as F901)
First checks, in this order
- Check the armature circuit for grounds and loose or intermittent connections.
- Check the current measuring module.
- Review the current regulator tuning.
- Check the SCR gate wire connections.
GF: Ground Fault
Hits OEE: AvailabilityWhat it means: The drive adds up the three output phase currents; the sum went above 50% of the drive rated output current, which points to current leaking to ground.[3]
Likely causes
- Motor winding or motor cable insulation failed to ground
- Electrical transients from brake contactor coils without surge suppression
First checks, in this order
- Disconnect the motor from the drive and test the motor and cable insulation with an insulation tester.
- Make sure R/C surge suppressors are fitted across all brake contactor coils.
GF: Ground Fault
Hits OEE: AvailabilityWhat it means: Current to ground on the drive output went above 50% of rated current. On this drive, ground fault detection is switched on with L08.09 = 1 and is available on models 2025 and 4014 or larger.[5]
Likely causes
- Motor winding or motor cable insulation failed to ground
- Electrical transients from brake contactor coils without surge suppression
First checks, in this order
- Disconnect the motor from the drive and test the motor and cable insulation with an insulation tester.
- Make sure R/C surge suppressors are fitted across all brake contactor coils.
- Check that L08.09 is set as intended.
OV: DC Bus Overvolt
Hits OEE: AvailabilityWhat it means: The main circuit DC bus voltage went above the overvoltage level. If it happens while the drive output is off (stopped), the same code shows as an alarm instead of a fault.[3]
Likely causes
- Deceleration too fast, so regenerated energy pumps up the DC bus
- Braking unit (DBU) or braking resistor not working or wrong size
- High incoming line voltage (the usual cause when it appears while stopped)
First checks, in this order
- Extend the deceleration time.
- Check braking unit (DBU) operation.
- Check the braking resistor.
- Check the line voltage.
oV: DC Bus Overvolt
Hits OEE: AvailabilityWhat it means: DC bus voltage went above about 410 V DC on 230 V class drives or about 820 V DC on 460 V class drives. A flashing oV means it happened while the output was off (minor fault).[5]
Likely causes
- Deceleration too fast for the load
- Braking unit (DBU) or braking resistor problem
- High incoming line voltage
- On a mechanical load brake hoist, a gear box problem
First checks, in this order
- Extend the deceleration time.
- Check braking unit (DBU) operation and the braking resistor.
- Check the line voltage.
- If it is a load brake hoist, check the gear box.
F408: EXCESSIVE PCU CEMF FAULT
Hits OEE: AvailabilityWhat it means: Motor counter EMF went above 118% of the rated AC input voltage, so the drive shuts down to keep from blowing fuses.[1]
Likely causes
- Low 3-phase input voltage
- Motor field current set too high, or the field regulator misbehaving
- Speed overshoot
- Field control tuning that lets CEMF overshoot
First checks, in this order
- Measure the 3-phase input voltage and correct it.
- Review the field settings #49, #50, #51, #52, #54 and #55.
- Correct speed overshoot with the velocity regulator adjustments.
UV1: DC Bus Undervolt
Hits OEE: AvailabilityWhat it means: DC bus undervoltage lasted more than 2 seconds while a RUN command was present.[3]
Likely causes
- Low or lost supply voltage
- Loose power wiring
- Crane collector system (runway conductors) losing contact
First checks, in this order
- Check the power wiring.
- Correct the line voltage.
- Check the collector system.
UV: DC Bus Undervolt
Warning: act before it becomes a stopWhat it means: DC bus undervoltage lasted more than 2 seconds while the drive was stopped. Shown as an alarm.[3]
Likely causes
- Low or lost supply voltage
- Blown branch fuse
- Crane collector system losing contact
First checks, in this order
- Check the power wiring.
- Replace any blown branch fuses.
- Check the collector system.
Uv1: DC Bus Undervolt
Hits OEE: AvailabilityWhat it means: Undervoltage lasted more than 2 seconds with a RUN command present. The trip level is below about 190 V DC on 230 V class drives and 380 V DC on 460 V class drives.[5]
Likely causes
- Low or lost supply voltage
- Loose power wiring
- Crane collector system losing contact
First checks, in this order
- Check the power supply wiring.
- Correct the line voltage.
- Check the collector system.
Uv: DC Bus Undervolt
Warning: act before it becomes a stopWhat it means: Flashing Uv: undervoltage lasted more than 2 seconds while stopped, with the same voltage levels as Uv1 (about 190 V DC on 230 V class, 380 V DC on 460 V class).[5]
Likely causes
- Low or lost supply voltage
- Blown branch fuse
- Crane collector system losing contact
First checks, in this order
- Check the power source wiring.
- Replace any blown branch fuses.
- Check the collector system.
F904: LOW LINE FAULT
Hits OEE: AvailabilityWhat it means: AC input dropped below 80% of the nominal line voltage set in #9 for 3 cycles in a row, or below 50% for one cycle. The current reference is forced to zero and the drive shuts down.[1][2]
Likely causes
- Supply voltage sag or outage
- Loose or failing connection upstream (breaker, transformer, fuses)
- #9 NOMINAL AC INPUT not matching the real line voltage
First checks, in this order
- Measure the 3-phase input under load and check the upstream breaker, transformer and fuse connections.
- Confirm #9 matches the real line voltage.
- Do not set #9 lower than the real voltage to hide this fault; Magnetek notes this pushes the drive into CEMF limiting and ripple faults (F909).
F406: 10% LOW LINE ALARM
Warning: act before it becomes a stopWhat it means: AC input sagged more than 10% below the nominal voltage in #9. The drive keeps running, but it is an early sign of future F904 shutdowns.[1]
Likely causes
- Weak or drooping supply
- Upstream connection or transformer problem
- #9 set higher than the real line voltage
First checks, in this order
- Check the incoming supply and connections before it turns into F904 trips.
- Confirm #9 NOMINAL AC INPUT is correct.
F903: LINE SYNC FAILURE
Hits OEE: AvailabilityWhat it means: The drive's phase-locked loop lost sync with the 3-phase input. The drive shuts down and needs a CPU reset. It often appears together with F904.[1][2]
Likely causes
- AC input power disturbances
- Pulsating armature current from poor tuning that disturbs the supply as seen by the drive (application note 103)
First checks, in this order
- Check the AC input power quality and connections.
- Look for F904 in the fault list at the same time.
- If it comes with F909, review the tuning: inertia #41 and stiffness #42.
UV2: CTL PS Undervolt
Hits OEE: AvailabilityWhat it means: The drive lost its internal 24 V logic power supply voltage.[3][5]
Also on: IMPULSE G+ Mini: same fault shown as Uv2 (CTL PS Undervolt).
Likely causes
- Low or interrupted supply voltage
- Power wiring or collector system problem
First checks, in this order
- Check the power wiring.
- Correct the line voltage.
- Check the collector system.
UV3: MC Answerback
Hits OEE: AvailabilityWhat it means: The pre-charge contactor opened while the drive was running.[3][5]
Also on: IMPULSE G+ Mini: same fault shown as Uv3 (MC Answerback).
Likely causes
- Supply voltage dip or interruption
- Power wiring or collector system problem
First checks, in this order
- Check the power wiring.
- Correct the line voltage.
- Check the collector system.
- Wait 30 to 45 seconds before restarting the drive.
F902: POWER SUPPLY FAULT
Hits OEE: AvailabilityWhat it means: The low voltage power supply (A4) output fell below 60% of rated. The drive shuts down and needs a CPU reset.[1]
Likely causes
- Loss of 115 VAC control power
- Short on the +5 V, +/-15 V or +24 V circuits, possibly in wiring outside the drive
- Failed power supply
- Blown fuse inside the power supply
First checks, in this order
- Check the 115 VAC control power at TB3 of power supply A4.
- Look for shorts on external logic wiring powered by the drive.
- Replace the power supply if the fault stays.
OH: Heatsnk Over temp
Warning: act before it becomes a stopWhat it means: Overheat pre-alarm: heatsink temperature passed the level set in L08-02. The manual marks it as alarm or fault; L08-03 picks what the drive does.[3][5]
Also on: IMPULSE G+ Mini: shown as flashing oH (Heatsnk Over temp), level set in L08.02.
Likely causes
- Drive cooling fan stopped
- High ambient temperature
First checks, in this order
- Check that the drive cooling fan runs.
- Reduce the ambient temperature.
- Check L08-02 and L08-03.
OH1: Heatsink MaxTemp
Hits OEE: AvailabilityWhat it means: Overheat fault: the measured heatsink temperature went above 105 °C, or the internal 24 V DC cooling fan failed.[3][5]
Also on: IMPULSE G+ Mini: same fault shown as oH1 (Heatsink MaxTemp), same 105 °C level.
Likely causes
- Cooling fan failure
- Dirt and debris on the heatsink
- Ambient temperature above specification
- Faulty heatsink thermistor
First checks, in this order
- Make sure the heatsink cooling fans run.
- Clean dirt and debris off the heatsink.
- Check that the ambient temperature is within specification.
- Replace the 24 V DC fan, then the heatsink thermistor(s) if the fault stays.
F908: OVER TEMPERATURE
Warning: act before it becomes a stopWhat it means: The calculated SCR junction temperature is above 125 °C, worked out from the heatsink thermistor and the armature current. The manual says it does not shut the drive down.[1]
Likely causes
- Ambient temperature too high
- Clogged cabinet air filter
- Clogged heatsink fins
- Failed cooling fan in the power cube
- Leakage between the heatsink thermistor and its leads (false readings)
First checks, in this order
- Check the machine room temperature.
- Clean or replace the cabinet air filter.
- Clean the heatsink fins.
- Replace failed cooling fans.
- If it repeats with no real heat, replace the thermistor and thermostats.
FAn: Cooling FAN Err
Hits OEE: AvailabilityWhat it means: The internal cooling fan has malfunctioned. L08-32 sets whether it acts as a fault or an alarm.[3]
Likely causes
- Worn or blocked cooling fan
- Fan at the end of its service life
First checks, in this order
- Cycle power to the drive.
- Check that the fan runs.
- Check fan run time in U04-03 and the fan maintenance timer in U04-04.
- Replace the fan.
OL1: Motor Overloaded
Hits OEE: AvailabilityWhat it means: Drive output went above the motor overload level. The manual lists it as fault or alarm.[3][5]
Also on: IMPULSE G+ Mini: same fault shown as oL1 (Motor Overloaded); setting is E02.01.
Likely causes
- Load too high
- Motor full load amps (E02-01) set wrong
First checks, in this order
- Check that E02-01 matches the motor nameplate full load amps.
- Reduce the load.
OL2: VFD Overloaded
Hits OEE: AvailabilityWhat it means: Drive output went above the drive's own overload level. The manual lists it as fault or alarm.[3][5]
Also on: IMPULSE G+ Mini: same fault shown as oL2 (VFD Overloaded).
Likely causes
- Load too high for the drive size
- Acceleration time too short
First checks, in this order
- Reduce the load.
- Extend the acceleration time.
F400: MOTOR OVERLOAD
Warning: act before it becomes a stopWhat it means: The drive has delivered too much motor current for too long (electronic motor overload). It does not stop the drive; it switches the ALARM relay output K2 so the car controller can act.[1]
Likely causes
- Dragging elevator brake
- Weakened motor field
- Overload time or level set wrong
First checks, in this order
- Check #83 MOTOR OVERLD TIME and #84 MOTOR OVERLD LEVEL.
- Check the elevator brake for drag.
- Check the motor field.
- See #182 for the alarm relay setting.
OH3: Motor Overheat 1
Warning: act before it becomes a stopWhat it means: The motor thermistor on the analog input reports motor overheating at the alarm level (L01-03). OH4 (Motor Overheat 2) is the fault level, set in L01-04.[3][5]
Also on: IMPULSE G+ Mini: same codes oH3 and oH4 (settings L01.03 and L01.04).
Likely causes
- Motor working too hard for its duty cycle
- Motor rated current (E02-01) set wrong
First checks, in this order
- Check the motor rated current value in E02-01.
- Increase the cycle time or reduce the load.
oL8: Klixon
Warning: act before it becomes a stopWhat it means: Klixon circuit alarm: the motor thermal switch circuit, wired to a digital input set to 56 or 57 (H01.xx), has opened.[5][3]
Also on: IMPULSE G+ / VG+ Series 4: same alarm shown as KLX (Klixon), input H01-0x = 56 or 57.
Likely causes
- Motor overheating
- Open or loose Klixon circuit wiring
First checks, in this order
- Check the motor for overtemperature.
- Check the Klixon circuit.
F941: MOTOR THERMOSTAT OPEN
Warning: act before it becomes a stopWhat it means: The drive sees the motor thermostat open between A4TB3(2) and A4TB3(8). It does not stop the drive; it switches the ALARM relay output K2.[1]
Likely causes
- Motor overheated
- Open thermostat wiring
- Faulty power supply input (if the circuit is closed but the fault stays)
First checks, in this order
- Let the motor cool and check the thermostat and its wiring to A4TB3.
- If the circuit is closed but the fault stays, replace the power supply.
- See #182 for the alarm relay setting.
PF: Input Phase Loss
Hits OEE: AvailabilityWhat it means: One phase of the drive's input power supply is open.[3][5]
Also on: IMPULSE G+ Mini: same fault shown as PF (Input Pha Loss).
Likely causes
- Blown line fuse
- Loose input terminal
- Lost supply phase
First checks, in this order
- Check the line voltage and fuses.
- Remove power and tighten the input terminals.
F910: BLOWN FUSE
Hits OEE: AvailabilityWhat it means: One or more of the three AC line fuses is open. Checked at power-up and during PCU Diagnostics (#998); at power-up the SCDU marks each blown fuse with the middle segment of a display digit.[1]
Likely causes
- Blown AC input fuse
- Power wiring problem
- Faulty DSPR power relay
First checks, in this order
- Remove power and check the line fuses.
- Check the power wiring.
- If all fuses test good, make sure 3-phase power and control power come on together (or the controller resets the drive after 3-phase power is applied).
- Check the power supply test points TP1 to TP4 on the Drive Control PCB: +24 V, +15 V, -15 V, +5 V within 5%.
LF: Output Phase Loss
Hits OEE: AvailabilityWhat it means: An open phase occurred on the drive output.[3][5]
Also on: IMPULSE G+ Mini: same fault shown as LF (Output Phase Loss).
Likely causes
- Broken wire in the output cable
- Open motor winding
- Loose terminal
First checks, in this order
- Check the output cable for broken wires.
- Check the motor for an open winding.
- Check for loose terminals.
F404: OPEN ARMATURE CIRCUIT FAULT
Hits OEE: AvailabilityWhat it means: A large current error lasted half a second, which usually means the armature circuit is open.[1]
Likely causes
- Blown DC link fuse F4
- Open or loose armature wiring
- Bad power poles in the DC loop contactor
First checks, in this order
- Check DC link fuse F4.
- Check the motor armature circuit wiring.
- Check the power poles in the DC loop contactor.
PGO-1-S / PGO-1-H: PG Open Ch1
Hits OEE: AvailabilityWhat it means: Encoder (pulse generator) feedback lost on the PG-X3 card in connector CN5-C: -S is found by software, -H by hardware. PGO-2-S and PGO-2-H mean the same for a card in CN5-B. F01-21 sets the stopping method or alarm only.[3]
Likely causes
- No encoder pulses while the drive is commanded to run
- Broken or shorted encoder wiring
- Misaligned pulse wheel, loose shaft coupling or failed sensor head
- Brake not opening, so the motor cannot turn
First checks, in this order
- Do not keep running the hoist after a PGO-x-H fault or repeated PGO-x-S faults.
- As a precaution, set Load Float Time C08-10 to zero until the cause is fixed.
- Check the pulse wheel alignment, shaft coupling and sensor head.
- Check each encoder wire for continuity, shorts between wires and shorts to shield or ground.
- Check that the brake opens, then restore C08-10.
DEV: Speed Deviation
Hits OEE: AvailabilityWhat it means: The gap between speed reference and encoder speed stayed above F01-27 for longer than F01-28, so the drive cannot follow the commanded speed. F01-26 sets fault or alarm.[3]
Likely causes
- Drive at its torque limit
- Snagged load or load above capacity
- Erratic or missing encoder pulses
- Brake not opening fully
- Acceleration or deceleration times shortened
First checks, in this order
- Stop using the hoist until the cause is found; set C08-10 to zero meanwhile.
- Check for a snagged load or a load above capacity.
- Check the encoder pulse wheel, coupling and cable.
- Check that the brake opens fully.
- Check accel and decel times B05-01, B05-02, C01-02, C01-04 and C01-05.
- Only after all that, raise F01-27, to no more than 30%.
OS: Over Speed
Hits OEE: AvailabilityWhat it means: The motor went above the overspeed level (F01-24) for the set time (F01-25). It is usually overshoot from a speed loop tuned too aggressively, or torque control mode running with no load. F01-23 sets the action.[3]
Likely causes
- Over-responsive speed regulator (ASR)
- Torque control mode with no load on the hook
- Wrong encoder pulses per revolution setting
First checks, in this order
- Check the speed regulator settings in group D04.
- Check F01-24 and F01-25.
- Check the encoder PPR in F01-01.
F97: OVERSPEED TRIP
Hits OEE: AvailabilityWhat it means: Encoder speed went above the trip level in #12, a percentage of rated motor RPM in #11.[1]
Likely causes
- #10, #11 or #12 set wrong
- Poor speed regulator tuning
- Speed reference above rated speed
- Intermittent encoder
First checks, in this order
- Check #10 ENCODER PPR, #11 RATED MOTOR RPM and #12 OVERSPEED %.
- Check speed regulator tuning #40, #41 and #42.
- Check that the speed reference does not exceed rated speed.
- Check the encoder and its connections.
- For a governor overspeed test, temporarily raise #12 above the governor trip speed.
F98: TACH/ENCODER LOSS
Hits OEE: AvailabilityWhat it means: Encoder speed does not match the speed the drive expects from the armature voltage.[1]
Likely causes
- Encoder not working or loose connection
- High motor resistance
- Contactor feedback at A1TB1-7 closing before the armature power poles
First checks, in this order
- Check that the encoder works and look for loose connections.
- On a high resistance motor, raise #14 V SENSE %; see also #15 T SENSE %.
- Make sure the contactor feedback at A1TB1-7 does not close before the armature power poles.
F99: REVERSE TACH/ENCODER
Hits OEE: AvailabilityWhat it means: The encoder and the motor voltage disagree on direction of rotation.[1]
Likely causes
- Encoder leads reversed
First checks, in this order
- Swap the encoder A and A NOT connections.
F410: SPEED ERROR FAULT
Hits OEE: AvailabilityWhat it means: A speed error larger than #100 lasted longer than #99 seconds, so the drive shut down.[1]
Likely causes
- Dragging brake
- Weak motor field
- Trip time or level set too tight
First checks, in this order
- Check the brake for drag.
- Check the motor field.
- Check #99 SPEED ERROR TRIP TIME and #100 SPEED ERROR TRIP LEVEL.
BE1: Rollback Detect
Hits OEE: AvailabilityWhat it means: After releasing the brake but before accelerating, the drive counted more encoder pulses than C08-05 within C08-04: the load rolled back. Usually the motor did not have enough torque to hold the load.[3]
Likely causes
- Not enough torque at brake release
- Noisy or damaged encoder cable
- Misaligned pulse wheel or loose shaft coupling
First checks, in this order
- Check the encoder cable for damage, noise and shield grounding.
- Check the pulse wheel and shaft coupling alignment.
- Only then adjust: keep C08-05 as close to 800 pulses as possible, and increase C08-21.
BE2: No Current
Hits OEE: AvailabilityWhat it means: Torque proving fault: before releasing the brake, the drive could not build torque up to C08-16 within the C08-02 timer. This often means a failed or slipping brake.[3]
Likely causes
- Brake slipping, worn or out of adjustment
- Motor not auto-tuned
- Open power limit switch
- Encoder cable or alignment problem
First checks, in this order
- Do not switch power off while it is active; move the load to a safe spot and lower it.
- Check brake operation, adjustment and wear, and run a brake torque test.
- Make sure the motor was auto-tuned and any power limit switch is closed.
- Check the encoder cable and pulse wheel alignment.
- Only then adjust: C08-02 not below 0.5 s, C04-02 not below 5, C08-16 not below 50.
BE3: Brake Release NG
Hits OEE: AvailabilityWhat it means: After releasing the brake and starting, the drive saw fewer encoder pulses than C08-07 within C08-06: the motor did not turn as expected. The load may drift until the brake sets again.[3]
Likely causes
- Brake not opening
- Misaligned pulse wheel or loose coupling
- Damaged encoder cable
First checks, in this order
- Check that the brake opens.
- Check the pulse wheel and coupling alignment.
- Check each encoder wire for continuity and shorts.
- Only then adjust: set C08-04 to the brake's mechanical delay, raise C08-06 to no more than 1 s, lower C08-07 to no less than 10 pulses.
BE4: Brake Answer 1
Warning: act before it becomes a stopWhat it means: At start, the brake answerback input did not arrive within C08-04 after the brake release command, so the brake is not confirmed released. The manual lists it as alarm and fault.[3][5]
Also on: IMPULSE G+ Mini: shown as flashing BE4 (Brake Answer 1), setting C08.04.
Likely causes
- Brake not releasing
- Fault in the brake answerback (feedback) circuit
- C08-04 shorter than the brake's real release time
First checks, in this order
- Check the brake answerback circuit.
- Increase C08-04.
- Check the input status in U01-10.
BE5: Brake Answer 2
Warning: act before it becomes a stopWhat it means: At stop, the brake answerback signal did not drop within C08-11 after the brake release command was removed, so the brake is not confirmed closed. It becomes a fault only if latched (L09-07, L09-08).[3][5]
Also on: IMPULSE G+ Mini: shown as flashing BE5 (Brake Answer 2), setting C08.11.
Likely causes
- Brake not setting
- Stuck brake answerback contact or wiring fault
- C08-11 shorter than the brake's real closing time
First checks, in this order
- Check the brake answerback circuit.
- Increase C08-11.
BE6: Brake Slipping
Warning: act before it becomes a stopWhat it means: Brake proving alarm: after commanding the brake to set, the drive counted more than C08-13 encoder pulses within C08-12, so the load is moving against the brake. The drive holds the load with Load Float during the alarm. It becomes a fault only if latched.[3][4]
Likely causes
- Failed, worn or badly adjusted brake
- Noisy or damaged encoder cable
- Misaligned pulse wheel or loose coupling
First checks, in this order
- Do not switch power off; move the load to a safe spot and lower it.
- Check brake operation, adjustment and wear.
- Check the encoder cable and the pulse wheel or coupling alignment.
- Only then adjust: set C08-11 to the brake's mechanical delay and increase C08-13.
BE7: Brake Welded
Hits OEE: AvailabilityWhat it means: At power-up the brake answerback is already on, which says the brake is not closed (or the answerback is stuck on).[3]
Likely causes
- Brake held open
- Welded or stuck answerback contact
- Answerback wiring fault
First checks, in this order
- Check that the brake is closed.
- Check the brake answerback circuitry.
BE8: Brake Slipping
Warning: act before it becomes a stopWhat it means: While not running, the encoder shows the load moving faster than C08-23 with the brake set. The drive goes into Load Float and keeps the brake closed. It becomes a fault only if latched.[3][4]
Likely causes
- Failed, worn or badly adjusted brake
- Noisy or damaged encoder cable
- Misaligned pulse wheel or loose coupling
First checks, in this order
- Do not switch power off; move the load to a safe spot and lower it.
- Check brake operation, adjustment and wear.
- Check the encoder cable and alignment.
- Check C08-23; if everything else checks out, the brake may need replacing.
BE0: Brake Ans Lost
Warning: act before it becomes a stopWhat it means: While running, the brake answerback input (H01-0x = 58) was lost. The manual lists it as alarm and fault.[3][5]
Also on: IMPULSE G+ Mini: shown as flashing BE0 (Brake Ans Lost).
Likely causes
- Brake answerback switch or wiring fault
- Brake starting to set during the run
First checks, in this order
- Check the brake answerback circuit.
- Check the input status in U01-10.
DIR: Direction Fault
Hits OEE: AvailabilityWhat it means: The drive found the hoist set up so that the FWD direction moves the hook DOWN.[3]
Likely causes
- Motor phase order or B03-04 setting gives the wrong direction
- Encoder direction not matching motor direction
First checks, in this order
- Verify the keypad shows FWD while moving UP; change B03-04 if it shows REV.
- Once the travel direction is verified correct, C08-34 = 0 disables DIR detection.
SNAP: Snapped Shaft
Hits OEE: AvailabilityWhat it means: A break in the drive train was detected by comparing two encoders (needs a second PG-X3 card). C11-09 sets fault or alarm.[3]
Likely causes
- Loose or broken coupling
- Loose encoder
- Broken shaft
First checks, in this order
- Check for a loose or broken coupling.
- Check for loose encoders.
- Check for a broken shaft.
F402: CONTACTOR FAULT
Hits OEE: AvailabilityWhat it means: The loop contactor auxiliary contact did not pick up or drop out within the allowed time (#102 selects the detection time).[1]
Likely causes
- Defective loop contactor auxiliary contact
- Contactor coil open or mechanically binding
- Defective pilot relay LPR
- Interference from other elevator relay contact circuits
First checks, in this order
- Check for proper feedback at TB1-7.
- Check the contactor for an open coil or binding.
- Check pilot relay LPR.
- Check #102 3S LOOP FLT.
F900: PCU LOOP FAULT
Hits OEE: AvailabilityWhat it means: The loop contactor did not close or opened unexpectedly, or motor voltage went above 30% of rated (#7) during Self-Tune (#997). The current reference is forced to zero and the drive shuts down.[1]
Likely causes
- Contactor auxiliary feedback circuit fault
- Contactor or LPR coil problem
- No power to LPR from the power supply (internal relay failure)
First checks, in this order
- Check the contactor auxiliary feedback circuit to TB1-7.
- Check the contactor and LPR coils.
- Check that LPR gets power from the power supply at TB3-5 (only momentary until F900 occurs); if not, replace power supply PCB A4.
F405: SAFETY CIRCUIT FAULT
Hits OEE: AvailabilityWhat it means: The safety circuit wired between TB3-1 and TB3-6 on the power supply opened unexpectedly while the drive was running. The check is off below the low speed threshold (#64).[1]
Likely causes
- Intermittent connection in the safety chain
- Safety chain closing less than 100 ms before the drive is enabled
First checks, in this order
- Check the safety chain for intermittent connections.
- Make sure the safety chain is closed at least 100 ms before the drive is enabled.
CE: Serial Com Err
Hits OEE: AvailabilityWhat it means: Serial communication was disrupted. The manual lists it as fault or alarm, set by the serial fault parameters in group H05.[3][5]
Also on: IMPULSE G+ Mini: CE (Modbus Com Err), serial data corrupted; check terminals R+, R-, S+, S- and H05.01 to H05.03 (the G+ Mini manual writes its parameters with a dot).
Likely causes
- Loose or damaged serial cable
- Wrong address, baud rate or parity
- Electrical noise on the communication line
First checks, in this order
- Check the serial connections.
- Check H05-01 to H05-05.
F117: 10 SEC COMM. START FAULT
Hits OEE: AvailabilityWhat it means: Serial communication did not start within 10 seconds after drive reset or power-up.[1]
Likely causes
- Host (car controller) not connected or not sending valid messages
- Grounding or noise problem on the serial link
- #110 set to serial mode (3) when serial control is not used
First checks, in this order
- Make sure the host is connected and sending valid messages.
- Look for and correct grounding and noise problems.
- If serial communication is not used, do not set #110 to 3.
F118: 150 MSEC COMM. MSG FAULT
Hits OEE: AvailabilityWhat it means: No valid serial message was received for more than 150 ms.[1]
Likely causes
- Host stopped sending or sends bad messages
- Grounding or noise problem on the serial link
First checks, in this order
- Make sure the host is connected and sending valid messages.
- Look for and correct grounding and noise problems.
- If serial communication is not used, do not set #110 to 3.
RR: DynBrk Transistr
Hits OEE: AvailabilityWhat it means: The internal braking transistor has failed.[3][5]
Also on: IMPULSE G+ Mini: same fault shown as rr (DynBrk Transistr).
Likely causes
- Braking resistor wired to the wrong terminals
- Wrong braking resistor
- Short circuit across the braking resistor
First checks, in this order
- Verify the external braking resistor is connected to the proper terminals.
- Confirm the proper resistor is installed.
- Check for a short circuit across the braking resistor.
F401: EXCESSIVE FIELD CURRENT
Hits OEE: AvailabilityWhat it means: Measured motor field current went above 125% of rated field current (#50).[1]
Likely causes
- Partially shorted motor field coil
- Wrong settings making the field current regulator unstable
- Wrong phasing on field module A3
- Wrong current tap at A3 TB4 or wrong A3 SW1 setting
- Motor field power circuit malfunction
First checks, in this order
- Check the motor field.
- Review #49, #50, #51, #52, #54 and #55.
- Verify A3 phasing, the TB4 current tap and SW1.
- Check module A3.
F905: FIELD LOSS
Hits OEE: AvailabilityWhat it means: Field current feedback fell below 80% of the expected value: #49 at top speed (field weakening), #50 during accel and decel (full field), #53 when standing. The drive shuts down.[1]
Likely causes
- Open motor field or field wiring
- Motor field control hardware failure
- Loss of power or wrong phasing to the field rectifier
First checks, in this order
- Check the motor field and its wiring for an open circuit.
- Check the AC supply and phasing to the field rectifier.
- Check the field control module.
F403: 5-MIN FULL FIELD FAULT
Hits OEE: AvailabilityWhat it means: The Drive and Field Enable input at TB1-9 stayed on for 5 minutes without the drive starting, which risks burning out the motor field.[1]
Likely causes
- Car controller relay logic leaving the enable on while idle
First checks, in this order
- Check the car controller relay logic that drives TB1-9.
F407: EXCESSIVE DCU CEMF ALARM
Warning: act before it becomes a stopWhat it means: Motor CEMF went above 109% of the measured AC input voltage. Warning only; the drive keeps running.[1]
Likely causes
- 3-phase input voltage drooped or is too low
- Motor field current too high (#49 weak field set point vs. desired top speed voltage)
- Field control tuning letting CEMF overshoot
First checks, in this order
- Check the input voltage.
- Check #49 against the motor voltage you want at top speed.
- Review #49, #50, #51, #52, #54 and #55.
F909: EXCESSIVE RIPPLE
Hits OEE: AvailabilityWhat it means: Armature current repeatedly showed a high peak-to-average ratio. Magnetek added it to protect motors from running on a missing SCR phase.[1][2]
Likely causes
- Poor tuning: inertia #41 too high, stiffness #42 or tach rate gain #107 too high
- Drive running into the CEMF limit
- Open SCR or loose gate wires
- Off-center encoder mounting
- Loose connections upstream, in the armature loop or worn motor brushes
- Repeated mechanical bumps in the hoistway
First checks, in this order
- Run PCU Diagnostics (#998) to look for hardware faults.
- Review tuning #41, #42 and #107.
- Check that the encoder is concentric with the motor shaft.
- Check 3-phase connections, the armature loop, brushes and SCR gate wires.
- Make sure all contactor and relay coils have noise suppressors.
F911: SHORTED SCR
Hits OEE: AvailabilityWhat it means: PCU Diagnostics (#998) found a short between the SCRs of an SCR/doubler pack. It is only checked when diagnostics run, and the drive must be powered down. F912 OPEN SCR is the companion result for an SCR that does not conduct.[1]
Likely causes
- Failed SCR or doubler pack
First checks, in this order
- Run PCU Diagnostics (#998); the optional handheld PCDU shows which SCR pair is bad.
- Replace the bad SCR pack.
- For F912, also check the SCR gate leads.
F411: MAX AUTO-RESETS ATTEMPTED
Hits OEE: AvailabilityWhat it means: More than 5 automatic resets were needed within 20 minutes of accumulated time, so auto reset (#101) stops and a manual reset is needed.[1]
Likely causes
- A repeating underlying fault
First checks, in this order
- Find the repeating fault in the Fault List (Function #0) or Error List (#800) and fix it.
- Reset the drive manually.
F926: PCU WATCHDOG TIMEOUT FAULT
Hits OEE: AvailabilityWhat it means: The power conversion processor was reset by its own watchdog timer. Usually caused by electrical noise. The drive must be powered down.[1]
Likely causes
- Electrical noise from relays without suppression
- 115 VAC and 24 VDC switched in the same relay without arc barriers
- Intermittent grounds in power or 24 VDC wiring
- Faulty EPROMs or sockets at U13, U14, U39 or U40
First checks, in this order
- Make sure all panel relays, including door operator relays, have working R/C coil suppression.
- Separate 115 VAC and 24 VDC contacts or add arc barriers.
- Check for intermittent grounds and verify the Drive Control PCB grounding and encoder wiring.
- Check the EPROMs and their sockets.
Prot: CORRUPTED NV RAM DATA
Hits OEE: AvailabilityWhat it means: At power-up the drive found parameter data lost or new (weak NVRAM battery in U56, new software or a new NVRAM chip) but cannot load defaults because the NV RAM PROTECT switch is on.[1]
Likely causes
- Weak battery inside NVRAM chip U56
- Software or NVRAM chip changed
First checks, in this order
- Set the NV RAM PROTECT switch to OFF and press CPU RESET to load defaults.
- Re-enter the parameters and save them with Function #994, then set the switch back to ON.
- Replace U56 every 8 years.
CPF06: EEPROM Error
Hits OEE: AvailabilityWhat it means: Data saved in EEPROM is corrupt, from an EEPROM circuit error or from power being switched off while parameters were saving.[3][5]
Also on: IMPULSE G+ Mini: CPF06 (EEPROM Data Error); cycle power, replace the drive if it stays.
Likely causes
- EEPROM or control circuit fault
- Power lost during a parameter save
First checks, in this order
- Turn off power and check the connection between the control board and the drive.
- After an interrupted save, reinitialize with A01-05 = 5432.
- If it continues, replace the control board or the drive (contact Magnetek).
HBB / HBBf: Hardware Base Block
Warning: act before it becomes a stopWhat it means: One of the Safe Disable inputs (H1, H2) is open, so the output is off, the motor coasts and the brake relay output opens.[3][5]
Also on: IMPULSE G+ Mini: Hbb (Hardware BB); if Safe Disable is not used, check that terminals HC and H1 are linked.
Likely causes
- External safety circuit opened
- Wrong sink/source selection for the digital inputs
- H1 and H2 jumpers missing when Safe Disable is not used
First checks, in this order
- Check the signal status at input terminals H1 and H2.
- Check the sink/source selection for the digital inputs.
- If Safe Disable is not used, check the H1 and H2 jumpers.
- If all is correct, replace the control board or the drive.
BB: Base Block
Warning: act before it becomes a stopWhat it means: A digital input commanded external base block: the output is off and the motor coasts. If RUN is still on when the base block input clears, the drive resumes at the commanded speed.[3][5]
Also on: IMPULSE G+ Mini: shown as flashing bb (Base Block); check H01.01 through H01.07.
Likely causes
- Base block input active
- Digital input programmed for base block by mistake
First checks, in this order
- Check H01-01 through H01-08 programming.
- Check the input status in U01-10.
EF1 to EF8: External Fault 1 to External Fault 8
Hits OEE: AvailabilityWhat it means: An external device wired to input terminal S1 to S8 signaled a fault; the number is the terminal. Fault or alarm is set in the External Fault Selection table.[3][5]
Also on: IMPULSE G+ Mini: EF1 to EF7 for terminals S1 to S7 (H01.01 to H01.07).
Likely causes
- Fault in the external device wired to that input
- Input programmed as external fault by mistake
First checks, in this order
- Check the programming of the matching input (H01-01 for S1 through H01-08 for S8).
- Check the condition of that input terminal (U01-10).
- Check the external device.
CF: Control Fault
Hits OEE: AvailabilityWhat it means: In Open Loop Vector control, the torque limit was reached for 3 seconds or longer.[5]
Likely causes
- Motor data not tuned
- Wrong motor parameters
First checks, in this order
- Perform auto-tuning.
- Check the motor parameters (E02 group) against the nameplate.
CRST: Cannot reset
Warning: act before it becomes a stopWhat it means: A fault reset was tried before the motor came to a complete stop, or while a RUN command was present during a fault.[5]
Likely causes
- Reset pressed while the motor was still coasting
- RUN command held during the reset
First checks, in this order
- Wait for the motor to come to a complete stop.
- Reset the fault before giving a RUN command.
dnE: Drive not ready
Warning: act before it becomes a stopWhat it means: A FWD or REV run command was already present when the drive powered up, so it will not run until the command is removed.[5][3]
Also on: IMPULSE G+ / VG+ Series 4: shown as Cant Run (Drive Not Ready), an alarm; toggle the run command, check H01-01 to H01-08, or set B03-10 to allow run at power up.
Likely causes
- Run command held on at power-up
- Input programming error
First checks, in this order
- Check the input terminals.
- Check H01.01 to H01.07 programming.
Log it, or the same alarm comes back
A fault stops the drive and with it the hoist, crane or line it moves, so in OEE terms it is a breakdown. An alarm lets the drive keep running, but its cause often becomes a fault later in the shift. Log faults with the minutes lost and alarms as early signs.
- Reason code: the code plus the drive, for example IMPULSE OL1, bay 3 crane hoist, so a motor overload that trips on the same lift every shift shows up as a pattern.
- Loss bucket: a stop that needs a reset, a part or a technician is an availability loss (breakdown). Stops shorter than your micro-stop threshold go to performance (minor stops). The six big losses page shows where each one belongs.
- What to count: how often each code fires per week and the minutes it costs. Two numbers a week turn "that alarm comes up sometimes" into a ranked list. The MTBF and MTTR calculator and the downtime cost calculator do the math.
The free OEE tracker logs each stop with its reason and turns the week into a downtime Pareto, so the code that costs the most rises to the top.
For drive faults across brands, fabrico.io has a VFD fault codes guide. A fault code tells you what the drive measured, not what happened at the machine in the seconds before. Fabrico's camera-based OEE software syncs camera video with machine data, so you can replay the moment the machine stopped next to the fault.
Frequently asked questions
Where is the Magnetek drive fault code list (PDF)?
Each drive's fault table is in its technical manual, which Columbus McKinnon (Magnetek's parent) posts free on the product pages at cmco.com. DSD 412: manual CS00407 rev 12, chapter Drive Faults, pages 82 to 91. IMPULSE G+/VG+ Series 4: Technical Manual 144-23910 R8, chapter 6 Troubleshooting, pages 190 to 209. IMPULSE G+ Mini: Technical Manual 144-25085 R8, section 6.1.3, pages 135 to 140. The Series 4 Quick Start Guide points to the technical manual for faults and alarms.
How do I reset a fault on a Magnetek IMPULSE drive?
Fix the cause first. Then press RESET on the keypad, switch on a digital input programmed for Fault Reset (setting 3F), or cycle power. On the G+ Mini a flashing minor fault clears by itself at the next run command. Automatic reset is set in group L09 (default 3 attempts). On Series 4, faults chosen in L09-07 and L09-08 latch once the automatic attempts run out: the RESET key is blocked and the fault survives a power cycle. Clear a latched fault by toggling a digital input set to 48 (Flt Latch Reset) on and off, or by pressing an F1 or F2 key programmed to 48 twice.
What do Magnetek DSD 412 faults mean?
The display shows F plus a number. Codes 13 to 26, 100 to 114 and 220 to 252 are control board (DCU) processor and memory errors, usually fixed by checking the EPROMs or replacing the Drive Control PCB. F97 to F99 are overspeed and encoder faults, F117 and F118 serial link faults, F400 to F414 drive faults such as motor overload, contactor, safety circuit and speed error, and F900 to F941 power converter (PCU) faults such as low line, field loss, blown fuse and SCR problems. Some only warn and do not shut the drive down: F400, F406, F407, F413, F907, F908 and F941.
How do I clear a DSD 412 fault and read the fault history?
Press DRIVE RESET (S1) on the power cube cover while the drive is not enabled, or have the car controller pulse the fault reset input at A1TB1-49. With Function #101 on, the drive resets itself 5 seconds after a fault; more than 5 counted resets within 20 minutes gives F411 and needs a manual reset. To read faults, select Function #0, press DATA/FCTN and step through with the arrow keys until End shows. It holds the first 16 faults since power-up or reset and is lost at power down. Function #800 shows the last 16 errors from battery-backed memory. Clearing a code from the list does not fix its cause.
What should I do after a BE6 or BE8 brake alarm on an IMPULSE hoist drive?
Treat it as a failed or slipping brake. Do not switch power off while the alarm is active, because the drive is holding the load with Load Float. Move the load to a safe place and lower it, then check brake operation, adjustment and wear, the encoder cable, and the encoder wheel or coupling alignment. Change detection settings (BE6: C08-11 and C08-13; BE8: C08-23) only after the hardware checks out.
Sources
Codes and meanings follow the manufacturer documentation below. Wording is ours, simplified for the shop floor; the manual for your exact model and software version wins if it differs.
- DSD 412 DC Elevator Drive Technical Manual, CS00407 rev 12, copyright Magnetek Elevator 2018, for software U39/40 97SA407Rv23 and U13/14 97SA404, hosted by Columbus McKinnon (cmco.com, DSD 412 product page)
- Application Note DSD 412-103: Ripple Current Fault (F909) in the DSD-412 DC Elevator Drive (listed as 11/2/2001 on the cmco.com DSD 412 product page), hosted by Columbus McKinnon (cmco.com)
- IMPULSE G+/VG+ Series 4 Adjustable Frequency/Vector Crane Controls Technical Manual, Part Number 144-23910 R8, November 2022, VFD firmware 14707 and 14750, copyright 2022 Magnetek, hosted by Columbus McKinnon (cmco.com, linked from the IMPULSE G+/VG+ Series 4 product page as Technical Manual Rev 8)
- IMPULSE G+/VG+ Series 4 Variable Frequency Drive Quick Start Guide, 144-27514 R1, August 2020, copyright 2020 Magnetek, hosted by Columbus McKinnon (cmco.com)
- IMPULSE G+ Mini Adjustable Frequency Crane Controls Technical Manual, Part Number 144-25085 R8, November 2020, VFD firmware 14515, copyright 2020 Magnetek, hosted by Columbus McKinnon (cmco.com, IMPULSE G+ Mini product page)
See the moment the drive tripped
Fabrico, a light MES with computer vision, syncs camera footage with machine and timeline data, so you can replay the exact moment a machine stopped and review the cause next to the drive's fault. Cameras also catch short stops and a line that is switched on but not producing, the losses nobody writes down. Machines connect through a PLC, a Fabrico IoT device or an AI camera.
Book a Fabrico demoRelated: SEW-Eurodrive fault codes · Lenze drive fault codes · overhead crane troubleshooting · VFD drive troubleshooting · electric motor
Other alarm code lookups: FANUC: servo amplifier · spindle amplifier · robot SRVO | Siemens: MICROMASTER 440 · MASTERDRIVES · SINAMICS G120 · SINAMICS V90 servo · SINAMICS V20 | ABB: ACS550 drive · ACS800 drive · robot IRC5 | Okuma: OSP alarms | Haas: alarm lookup | Mitsubishi: MELSERVO servo · FR-D700 and FR-E700 inverters · FX PLC | Allen-Bradley: Kinetix and Ultra3000 · MicroLogix · PowerFlex 753 and 755 · PowerFlex 70 and 700 · 1336 and 1305 | Yaskawa: V1000 drive · SERVOPACK servo · Motoman robot | Delta: VFD drives · ASDA servo | Eaton: DC1 and SVX9000 drives | Control Techniques: Commander SK and M200 | Kollmorgen: AKD servo | Lenze: SMVector, 8200, 8400, i500 | Omron: MX2 and RX inverters · G5 and 1S servo | WEG: CFW500, CFW300, CFW11, CFW08 | Hitachi: WJ200 inverter | Toshiba: E3, Q9, P9, S15, nC3, AS3 | AutomationDirect: GS10, GS20, GS4, GS1 to GS3 | SANYO DENKI: SANMOTION servo | Parker: SSD 590+, 690+, AC10 | KEB: COMBIVERT F5 | Epson: robot RC700, RC90 | B&R: ACOPOS servo | Schneider Electric: Lexium 32 servo | Bosch Rexroth: IndraDrive | Vacon: NX, VACON 100 and 20 | Fuji Electric: FRENIC-Mini, Multi, Ace, MEGA | LS Electric: S100, G100, iG5A | Panasonic: MINAS A6 and A5 servo | Invertek: Optidrive E3, P2, Eco | SEW-Eurodrive: MOVITRAC B and MOVIDRIVE B
Related tools: full troubleshooting directory · OEE calculator · downtime cost · MTBF / MTTR · glossary